background image

34

the last 7 days - in case it is set to start once a week. If the 

function is activated, it is performed every day at 3:00 a.m. if 

set to start every day, or on Wednesdays at 3:00 a.m. if set to 

start every week. 

The maximum duration of the anti-legionella cycle is 4 

hours; if this function is interrupted because the time has 

been exceeded, the error message “ANTI-LEGIONELLA 

FUNCTION NOT COMPLETED” will appear on the display.

The system will attempt to execute the function again the 

following day.

 

b

The function is not performed when the boiler is OFF.

 

b

In the INFO menu, the  NEXT ANTILEGIO  parameter 

indicates the number of days left until the next anti-

legionella cycle.

This function can be interrupted in advance in two different 

ways:

 

-

set the boiler to OFF 

or

 

-

select STATE 

 DHW 

 ANTILEGIO CUT OFF.

If the function is interrupted, it will be repeated at the same 

time the next day, even if weekly programming is active.

BOILER

STATE

MAIN ZONE

BOILER

MAIN ZONE

STATE

DHW

STATE

DHW

ANTILEGIO CUT OFF

To activate the function:

 

-

select TECHNICAL 

 ANTI-LEGIONELLA

ANTI-LEGIONELLA

COMBUSTION ANALYSIS

WEATHER COMPENSATION

RANGE RATED

TECHNICAL

INSTALLER

CALIBRATION

 

-

personalise the following parameters:

  FUNCTION NOT ACTIVE: the function will not be executed

  DAILY FUNCTION: the anti-legionella cycle is executed 

every day at the time set in the ANTILEGIO TIME parameter

  WEEKLY FUNCTION: the anti-legionella cycle is executed 

every Wednesday at the time set in the ANTILEGIO TIME 

parameter

  ANTILEGIO FLOW: allows you to set the boiler delivery 

temperature to the storage tank during the execution of the 

anti-legionella function (default value 80°C)

  ANTILEGIO TIME: allows you to set the function execution 

time (default setting 03:00 AM)

  ANTILEGIO TEMP: allows you to set the storage tank 

retention temperature during the execution of the anti-

legionella function (70°C).

STATE

MAIN ZONE

ANTILEGIO TIME

ANTILEGIO

MAIN ZONE

FUNCTION NOT ACTIVE

MAIN ZONE

DAILY FUNCTION

MAIN ZONE

WEEKLY FUNCTION

MAIN ZONE

ANTILEGIO TEMP

MAIN ZONE

ANTILEGIO FLOW

INSTALLER

The water tank retention time for anti-legionella varies 

according to the temperature value set in the ANTILEGIO 

TEMP parameter, as shown in the table:

ANTILEGIO TEMPERATURE

Retention 

temperature

ANTILEGIO TEMPERATURE < 58°C

180 min

58°C < ANTILEGIO TEMPERATURE < 62°C

60 min

62°C < ANTILEGIO TEMPERATURE < 66°C

30 min

66°C < ANTILEGIO TEMPERATURE < 75°C

15 min

ANTILEGIO TEMPERATURE > 75°C

1 min

6.2.4  EMBEDDED CLOCK HEATING SCHEDULE

When the embedded clock is enabled (POR=1 - see above), a 

default heating schedule is used to manage the ON/OFF timings 

for each day of the week (operating mode = AUTO). if necessary, 

the default heating schedule can be changed according to the 

User’s needs. Refer to “2.10 TIME SCHEDULE” (User section) 

for detailed instruction/guidance on how to access and change the 

default heating schedule.

18/05/2013

12:17

30

°C

.3

1.3 bar

MENU

INFO

SET

FRI

HOT WATER TEMPERATURE

STATE

PLANT

MON

SETTINGS

MENU

SELECT OPTION

TIME SCHEDULE

MON

18/11/2013

12:17

MAIN

SELECT THE ZONE

SCHEDULE

07:30
11:30
18:00

08:30
13:30
22:30

SELECT

A DAY

START

MAIN 

THURSDAY

END

ZONE SCHEDULE

6.2.5  SETTING THE THERMOREGULATION

Thermoregulation (weather compensation) controlled by the 

appliance, can only be enabled if an external sensor has 

been installed and connected to the M4 terminal strip. 

When the presence of an external sensor is detected, 

the appliance immediately enables the thermoregulation 

function and calculates a required outlet (flow) temperature 

that is based on the external temperature and the chosen 

climatic curve.  The temperature measured by the outdoor 

temperature sensor is displayed on the initial page in the top 

right, alternating with the display of the time.

When thermoregulation is enabled (outdoor temperature 

sensor present), the algorithm for automatically calculating 

the outlet setpoint depends on the type of heat request.

In any case, the thermoregulation algorithm will not directly 

use the outdoor temperature, but rather a calculated outdoor 

temperature that takes into account the building’s insulation: 

in buildings that are well insulated, the outdoor temperature 

variations will have less impact than those that are poorly 

insulated by comparison. Enabling THERMOREGULATION 

occurs in the following way:

 - select TECHNICAL 

 WEATHER COMPENSATION

PARAMETERS

WEATHER COMPENSATION

RANGE RATED

TECHNICAL

INSTALLER

CALIBRATION

INSTALLATION

Using the REC10 it is possible to set the value of the following 

parameters:

BUILDING TYPE:

  it  is indicative of the frequency with 

which the value of the calculated outdoor temperature for 

thermoregulation is updated, a low value for this setting will 

be used for buildings that have little insulation.

Setting range:   [5min - 20min]

Factory setting: [5min]

REACTIVITY EXT SENSOR:

 it  is an indication of the 

speed with which variations of the measured outdoor 

temperature affect the calculated outdoor temperature value 

for thermoregulation, low values indicate high speeds.

Setting range:   [0 - 255]

Factory setting:  [20]

To change the value of the previous parameters, proceed as 

described below:

 - select TECHNICAL 

 WEATHER COMPENSATION 

 BUILDING TYPE rather than REACTIVITY EXT 

SENSOR

 

-

set the desired value.

Note:

 The value of the calculated outdoor temperature used 

by the thermoregulation algorithm is displayed in the INFO 

menu under T EXT FOR THERMOREG.

Содержание 41-364-13

Страница 1: ...d member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK UNICA MAX 20S NG G C N 41 364 13 UNICA MAX 30S NG G C N 4...

Страница 2: ...s 1 2 ELECTRICAL SUPPLY Please ensure that this appliance has been properly connected to the electrical supply by means of a double pole isolator or un switched socket and that the correct size of fus...

Страница 3: ...shing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes default value parameter water tank type 0 If w...

Страница 4: ...OP TIME 20 00 00 00 23 59 USER only if NIGHT REDUCTION active 1 MENU DEFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FU...

Страница 5: ...essing the ok and back keys it will be possible to select the other zones in this sequence only if added and configured with the REC10 H PLANT MAIN ZONE ZONE 1 ZONE 2 The TIME AND DATE DAYLIGHT SAVING...

Страница 6: ...and confirm Once the selection is confirmed the display returns to the SET screen If the selection is cancelled or the back key is pressed you return to the previous SET screen SET HEATING 78 0 C SET...

Страница 7: ...t time is replaced with the boiler flow temperature and turns on the icon concerning the type of request in progress A system efficiency indicator is also displayed at the top of the screen HIGH EFFIC...

Страница 8: ...er to confirm that the operation has been completed successfully the display will show the table with the selected time frame flashing just before deleting it from the table START MAIN THURSDAY ARE YO...

Страница 9: ...l E090 fault flue gases probe flue gases overtemperature probe temporary final E091 clean primary heat exchanger temporary E099 reset attempts exhausted boiler blocked definitive not resettable water...

Страница 10: ...phase with the ignition of the burner at minimum output which is maintained until the outlet water temperature reaches 35 C DHW frost protection the function starts if the temperature measured by the...

Страница 11: ...ous horizontal or vertical applications These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral pa...

Страница 12: ...abled Ignitionissensedbytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minu...

Страница 13: ...ance for the insertion of a FGA probe This can be reduced to 4mm if a removal panel enables the required 100mm When installed in a cupboard this dimension can be reduced to 4mm provided that the requi...

Страница 14: ...ime P4 19 5 31 2 kW At 30 of rated heat output and low temperature regime P1 6 5 10 5 kW Useful efficiency At rated heat output and high temperature regime 4 87 8 87 9 At 30 of rated heat output and l...

Страница 15: ...CULATOR WITH CONSTANT T MODE 2 DUTY CYCLE PUMP 40 In this mode the installer sets the T value to be maintained between flow and return e g by entering a value 10 the circu lator speed will change to o...

Страница 16: ...ning in the car port into the building 1200 mm M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm P From a structure to the side of the vertic...

Страница 17: ...ne the number 1 or 2 is flashing Only if heat pump is present This icon indicates that cooling is active in the SUMMER state If a cooling request from the main zone is in progress the icon is flashing...

Страница 18: ...he signal on the main screen corresponds to the highest priority in the following ascending order Grey Green Yellow and Red The configuration MENU is organised with a multi access level tree structure...

Страница 19: ...I PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE only mixing zones with ACT...

Страница 20: ...IENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTALLER if request type AMBIENT PROBE or REC10CH OFFSET 20 C 20 C 40 C INSTALLER if request type AMBIENT PROBE or REC10CH COOLING 18 C 4 C 20 C INSTAL...

Страница 21: ...SABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 prese...

Страница 22: ...E FUNCTION INSTALLER ACTIVATE FUNCTION INSTALLER FUNCTION SETTINGS SERVICE TFMIN 20 C 15 C 30 C SERVICE TFMAX 35 C 30 C 55 C SERVICE COMBUSTION MONITORING SERVICE GAS TYPE NATURAL GAS NATURAL GAS LPG...

Страница 23: ...CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER PUMP DUTY CYCLE INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER PARAMETERS CALIBRATION 8 FRI 09 04 2021 12 17 MENU INFO SET AIR PURGING...

Страница 24: ...rves more than one appliance it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time NOTE It is recognised that pressure loss through the gas c...

Страница 25: ...S 813 4A 1 RELATED DOCUMENTS The installation of this boiler must be in accordance with the relevant requirements of the local building regulations the current ETCI National Rules for Electrical Insta...

Страница 26: ...provided see fig 6 You shouldensurethismethodoffillingcomplieswiththelocalwater authority regulations 4A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an in...

Страница 27: ...ystem or download the instructions from the Vokera website The appliance flue outlet elbow can be rotated through 360 on its vertical axis In addition the flue may be extended from the outlet elbow in...

Страница 28: ...hat all seals are located properly You must ensure that the entire flue system is properly supported and connected Seal the flue assembly to the wall using cement or a suitable alternative that will p...

Страница 29: ...hers before tightening the valve to the appliance NOTE It will be necessary to hold the valve with one spanner whilst tightening with another Gas cock C H flow valve C H return valve Fig 20 5 6 1 GAS...

Страница 30: ...ust be 3 core flexible sized 0 75mm to BS 6500 or equivalent Wiring to the appliance must be rated for operation in contact with surfaces up to 90 C ModBus 485 Connection CE4 Carry out the connections...

Страница 31: ...e the fly lead with an alternative method of connection to the electrical supply 5 7 3 CONNECTING A 230V SUPPLY TO THE APPLIANCE PCB WARNING Isolate the appliance from the electrical supply before car...

Страница 32: ...AND DATE Navigate with the keys to set the values 12 17 ENTER TIME AND DATE TIME DATE USE THE ARROWS TO MODIFY 18 11 2013 Note it is possible to change the TIME and DATE DAYLIGHT SAVINGS TIME setting...

Страница 33: ...tantaneously interrupted 6 2 2 CONFIGURATION OF THE ZONE It is possible to customise the management of the heating zone by accessing the ZONES MANAGER menu Access to menu TECHNICAL INSTALLATION ZONES...

Страница 34: ...N OFF timings for each day of the week operating mode AUTO if necessary the default heating schedule can be changed according to the User s needs Refer to 2 10 TIME SCHEDULE User section for detailed...

Страница 35: ...ot produce a switch off but a reduction parallel translation of the climatic curve on NIGHT level 16 C Also in this case the user can indirectly modify the value of the HEATING setpoint inserting once...

Страница 36: ...alue within the range 40 C 80 5 C for high temperature systems or 20 C 45 C for low temperature systems default is high temperature DHW SET HEATING 6 5 ADJUSTING THE HEATING WATER TEMPERATURE WITH AN...

Страница 37: ...the table on the side Accessing the INFO menu from the main page of the REC10 it is possible to display the TIME FUNC SCREED HEATING value regarding the number of hours since the start of the function...

Страница 38: ...present Reset function In order to reset the boiler s operation in the event of a fault it is necessary to access the fault description screen If the lockout is of a non volatile type that requires a...

Страница 39: ...rm E097 iono alarm E085 combustion fault high CO These are temporary alarms that if they occur several times in an hour they become definitive the last error to occur is displayed and is followed by a...

Страница 40: ...lectronics boards AKM and REC 10 MASTER will require the re programming of these parameters Set SERVICE password Select TECHNICAL COMBUSTION MONITORING AIR PURGING CYCLE PARAMETERS EXHAUST PROBE RESET...

Страница 41: ...f replacement it is necessary to always ensure that it is correctly positioned and to strictly observe the reference shown in the figure detector electrode ionisation sensor flame ignition electrode a...

Страница 42: ...ct the internal components and electrical wiring for any defect or deterioration 4 Visually check for any dirt or debris within the condensate trap the trap is translucent and can be checked visually...

Страница 43: ...nt hysterisis the burner will re light NOTE Ifburnerignitionisnotdetectedatthefirstattempt theappliance will repeat the ignition sequence another two times 3 times in total before going to lockout Whe...

Страница 44: ...continuity 8 7 APPLIANCE STATUS AND FAULT CODES When the boiler detects a temporary fault condition the appropriate code is shown If when the fault is final the pump will perform 30 to 60 second post...

Страница 45: ...iance The UNICA MAX S system boilers incorporate an internal relay that enables a direct switched 230v supply to be used to generate a heating or hot water request from an external control system such...

Страница 46: ...T Pressure transducer MOD Modulator F Lv Fan signal control M GREY BROWN BLUE ORANGE ORANGE BLUE BROWN GREY M N L 230 V Fuse 3 AMP NO NC COM NO NC COM ROOM THERMOSTAT CYLINDER THERMOSTAT M NO NC COM...

Страница 47: ...SC2 blue S E brown yellow green N F X6 3 1 red 24 Vdc yellow B orange A black red 24 Vdc yellow B orange A black REC black orange A yellow B red 24 Vdc A B CE4 removable connector positioned under she...

Страница 48: ...E password 3 Select TECHNICAL COMBUSTION MONITORING GAS TYPE LPG ERROR HISTORY EXHAUST PROBE RESET AIR PURGING CYCLE PARAMETERS COMBUSTION MONITORING SERVICE TECHNICAL BOILER TYPE COMBUSTION OFFSET GA...

Страница 49: ...h section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES I Is s C CO O 3 35 50 0p pp pm m a an nd d C CO O C CO O2 2 r ra at...

Страница 50: ...turers recommendations at least annually This must be carried out by a competent Gas Safe registered engineer The service details should be recorded on the Benchmark Service and Interim Boiler Work Re...

Страница 51: ...no what is the maximum central heating output selected kW Dynamic gas inlet pressure mbar C Central heating return temperature C System correctly balanced rebalanced Yes COMBINATION BOILERS ONLY Is t...

Страница 52: ...eer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas...

Страница 53: ...eer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas...

Страница 54: ...missioning sheet RGII Installation Certificate ROI the warranty will commence from the date of manufacture as detailed on the appliance data plate 6 To qualify for the full term of warranty the boiler...

Страница 55: ...dhered to f To any other costs or expenses caused by or arising as a result of the breakdown of a Vok ra Boiler g To any costs incurred during delays in fixing reported faults 10 We reserve the right...

Страница 56: ...Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the right to change specification without prior notice Consumers statutory rights are not affected Company Reg...

Отзывы: