background image

24

4.  SECTION - GENERAL REQUIREMENTS (UK)

BS 5440

PART 1

FLUES

BS 5440

PART 2

FLUES & VENTILATION

BS EN 12828

DESIGN FOR WATER-BASED HEATING SYSTEMS

BS 6798

INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 70kW

BS 6891

LOW PRESSURE INSTALLATION PIPES

This appliance must be installed by a competent person in 

accordance with the Gas Safety (Installation & Use) Regulations.

4.1  RELATED DOCUMENTS

The installation of this boiler must be in accordance with the 

relevant requirements of the Gas Safety (Installation & Use) 

Regulations, the local building regulations, the current I.E.E. 

wiring regulations, the bylaws of the local water undertaking, the 

Building Standards (Scotland) Regulation, and Building Standards 

(Northern Ireland) Regulations. It should be in accordance also 

with any relevant requirements of the local authority and the 

relevant recommendations of the following British Standard 

Codes of Practice.

ATTENTION

The use of PPE (Personal Protective Equipment) such as but not 

limited to gloves, mask, safety glasses, etc. is strongly recom-

mended whenever carrying out the installation, repair, or mainte-

nance of this appliance – please pay particular attention to:

•  Sharp edges that may be encountered when:- handling or 

lifting the appliance, removing parts, etc. during installation 

and maintenance

•  Airborne particles that may be released and/or disturbed when 

cleaning or removing components during maintenance

•  Water treatment chemicals that could have been added to 

the system water may spill from the appliance and or com-

ponents during maintenance

Please refer to an appropriate Health and Safety document 

such as HSE L23 (UK) or S.I. 299 (Ireland), for more detailed 

advice on safe working practices and procedures. 

4.2  LOCATION OF APPLIANCE

The appliance may be installed in any room or internal space, 

although particular attention is drawn to the requirements 

of the current I.E.E. wiring regulations, and in Scotland, the 

electrical provisions of the Building Regulations, with respect 

to the installation of the appliance in a room or internal space 

containing a bath or shower. When an appliance is installed 

in a room or internal space containing a bath or shower, the 

appliance or any control pertaining to it must not be within 

reach of a person using the bath or shower (refer to IEE regs). 

The location chosen for the appliance must permit the 

provision  of  a  safe  and  satisfactory  flue  and  termination. 

The location must also permit an adequate air supply for 

combustion purposes and an adequate space for servicing 

and air circulation around the appliance. Where the 

installation of the appliance will be in an unusual location 

special procedures may be necessary, BS 6798 gives detailed 

guidance on this aspect. A compartment used to enclose the 

appliance must be designed and constructed specifically for 

this purpose. An existing compartment/cupboard may be 

utilised provided that it is modified to suit

. Details of essential 

features of compartment/cupboard design including airing 

cupboard installations are given in BS 6798. This appliance is 

not configured for external installation applications

.

4.3  GAS SUPPLY

The gas meter – as supplied by the gas supplier – must be checked 

to ensure that it is of adequate size to deal with the maximum rated 

input of all the appliances that it serves. Installation pipes must 

be fitted in accordance with BS 6891

. Pipe work from the meter 

to the appliance must be of adequate size. Pipes of a smaller 

size than the appliance gas inlet connection must not be used. 

The installation must be tested for soundness in accordance with 

BS6891.

 

If the gas supply serves more than one appliance, it 

must be ensured that an adequate supply is maintained to each 

appliance when they are in use at the same time.

NOTE:

 It is recognised that ‘pressure loss’ through the gas cock 

and gas valve may result in a pressure drop of approximately 

2mbar between the gas meter and gas valve inlet test point; this 

will not impair the performance of the appliance, provided that a 

dynamic pressure of 18mbar is available at the appliance inlet.

4.4  FLUE SYSTEM

The terminal should be located where the dispersal of combustion 

products is not impeded and with due regard for the damage 

and discoloration that may occur to building products located 

nearby. The terminal must not be located in a place where it 

is likely to cause a nuisance (see fig. 5

). In cold and/or humid 

weather, water vapour will condense on leaving the terminal; 

the effect of such pluming must be considered

.

If installed less than 2m above a pavement or platform to which 

people have access (including balconies or flat roofs) the terminal 

must be protected by a guard of durable material. The guard 

must be fitted centrally over the terminal. Refer to BS 5440 

Part 1, when the terminal is 0.5 metres (or less) below plastic 

guttering or 1 metre (or less) below painted eaves.

4.5  AIR SUPPLY

The following notes are intended for general guidance only. This 

appliance is a room-sealed, fan-flued boiler, consequently it 

does not require a permanent air vent for combustion air supply. 

When installed in a cupboard or compartment, ventilation for 

cooling purposes is also not required.

4.6  WATER CIRCULATION

Detailed recommendations are given in BS EN 12828 and BS 

6798. The following notes are for general guidance only.

4.6.1  PIPEWORK

It is recommended that copper tubing to BS 2871 Part 1 is used 

in conjunction with soldered capillary joints.  Where possible 

pipes should have a gradient to ensure air is carried naturally to 

air release points and that water flows naturally to drain cocks

Except where providing useful heat, pipes should be insulated to 

avoid heat loss and in particular to avoid the possibility of freezing. 

Particular attention should be paid to pipes passing through 

ventilated areas such as under floors, loft space, and void areas

.

4.6.2  AUTOMATIC BY-PASS

The appliance has a built-in automatic by-pass, consequently there 

is no requirement for an external by-pass, however the design 

of the system should be such that it prevents boiler ‘cycling’.

4.6.3  DRAIN COCKS

These must be located in accessible positions to facilitate draining 

of the appliance and all water pipes connected to the appliance. The 

drain cocks must be manufactured in accordance with BS 2879.

4.6.4  AIR RELEASE POINTS

These must be positioned at the highest points in the system 

where air is likely to be trapped. They should be used to expel 

trapped air and allow complete filling of the system

.

4.6.5  EXPANSION VESSEL

The appliance has an integral expansion vessel to accommodate 

the increased volume of water when the system is heated. 

Refer to the specification table for more detailed information

.

4.6.6  FILLING POINT

A method for initial filling of the system and replacing water lost 

during servicing etc. directly from the mains supply, should be 

provided (see fig. 6

). 

This method of filling complies with the 

current Water Supply (Water Fittings) Regulations 1999 and 

Water Bylaws 2000 (Scotland).

4.6.7  LOW PRESSURE SEALED SYSTEM

An alternative method of filling the system would be from an 

independent make-up vessel or tank mounted in a position at 

least 1 metre above the highest point in the system and at least 

5 metres above the boiler (see fig. 7

).

The cold feed from the make-up vessel or tank must be fitted 

with an approved non-return valve and stopcock for isolation 

purposes. The feed pipe should be connected to the return pipe 

as close to the boiler as possible.

Содержание 41-364-13

Страница 1: ...d member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK UNICA MAX 20S NG G C N 41 364 13 UNICA MAX 30S NG G C N 4...

Страница 2: ...s 1 2 ELECTRICAL SUPPLY Please ensure that this appliance has been properly connected to the electrical supply by means of a double pole isolator or un switched socket and that the correct size of fus...

Страница 3: ...shing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes default value parameter water tank type 0 If w...

Страница 4: ...OP TIME 20 00 00 00 23 59 USER only if NIGHT REDUCTION active 1 MENU DEFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FU...

Страница 5: ...essing the ok and back keys it will be possible to select the other zones in this sequence only if added and configured with the REC10 H PLANT MAIN ZONE ZONE 1 ZONE 2 The TIME AND DATE DAYLIGHT SAVING...

Страница 6: ...and confirm Once the selection is confirmed the display returns to the SET screen If the selection is cancelled or the back key is pressed you return to the previous SET screen SET HEATING 78 0 C SET...

Страница 7: ...t time is replaced with the boiler flow temperature and turns on the icon concerning the type of request in progress A system efficiency indicator is also displayed at the top of the screen HIGH EFFIC...

Страница 8: ...er to confirm that the operation has been completed successfully the display will show the table with the selected time frame flashing just before deleting it from the table START MAIN THURSDAY ARE YO...

Страница 9: ...l E090 fault flue gases probe flue gases overtemperature probe temporary final E091 clean primary heat exchanger temporary E099 reset attempts exhausted boiler blocked definitive not resettable water...

Страница 10: ...phase with the ignition of the burner at minimum output which is maintained until the outlet water temperature reaches 35 C DHW frost protection the function starts if the temperature measured by the...

Страница 11: ...ous horizontal or vertical applications These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral pa...

Страница 12: ...abled Ignitionissensedbytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minu...

Страница 13: ...ance for the insertion of a FGA probe This can be reduced to 4mm if a removal panel enables the required 100mm When installed in a cupboard this dimension can be reduced to 4mm provided that the requi...

Страница 14: ...ime P4 19 5 31 2 kW At 30 of rated heat output and low temperature regime P1 6 5 10 5 kW Useful efficiency At rated heat output and high temperature regime 4 87 8 87 9 At 30 of rated heat output and l...

Страница 15: ...CULATOR WITH CONSTANT T MODE 2 DUTY CYCLE PUMP 40 In this mode the installer sets the T value to be maintained between flow and return e g by entering a value 10 the circu lator speed will change to o...

Страница 16: ...ning in the car port into the building 1200 mm M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm P From a structure to the side of the vertic...

Страница 17: ...ne the number 1 or 2 is flashing Only if heat pump is present This icon indicates that cooling is active in the SUMMER state If a cooling request from the main zone is in progress the icon is flashing...

Страница 18: ...he signal on the main screen corresponds to the highest priority in the following ascending order Grey Green Yellow and Red The configuration MENU is organised with a multi access level tree structure...

Страница 19: ...I PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE only mixing zones with ACT...

Страница 20: ...IENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTALLER if request type AMBIENT PROBE or REC10CH OFFSET 20 C 20 C 40 C INSTALLER if request type AMBIENT PROBE or REC10CH COOLING 18 C 4 C 20 C INSTAL...

Страница 21: ...SABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 prese...

Страница 22: ...E FUNCTION INSTALLER ACTIVATE FUNCTION INSTALLER FUNCTION SETTINGS SERVICE TFMIN 20 C 15 C 30 C SERVICE TFMAX 35 C 30 C 55 C SERVICE COMBUSTION MONITORING SERVICE GAS TYPE NATURAL GAS NATURAL GAS LPG...

Страница 23: ...CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER PUMP DUTY CYCLE INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER PARAMETERS CALIBRATION 8 FRI 09 04 2021 12 17 MENU INFO SET AIR PURGING...

Страница 24: ...rves more than one appliance it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time NOTE It is recognised that pressure loss through the gas c...

Страница 25: ...S 813 4A 1 RELATED DOCUMENTS The installation of this boiler must be in accordance with the relevant requirements of the local building regulations the current ETCI National Rules for Electrical Insta...

Страница 26: ...provided see fig 6 You shouldensurethismethodoffillingcomplieswiththelocalwater authority regulations 4A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an in...

Страница 27: ...ystem or download the instructions from the Vokera website The appliance flue outlet elbow can be rotated through 360 on its vertical axis In addition the flue may be extended from the outlet elbow in...

Страница 28: ...hat all seals are located properly You must ensure that the entire flue system is properly supported and connected Seal the flue assembly to the wall using cement or a suitable alternative that will p...

Страница 29: ...hers before tightening the valve to the appliance NOTE It will be necessary to hold the valve with one spanner whilst tightening with another Gas cock C H flow valve C H return valve Fig 20 5 6 1 GAS...

Страница 30: ...ust be 3 core flexible sized 0 75mm to BS 6500 or equivalent Wiring to the appliance must be rated for operation in contact with surfaces up to 90 C ModBus 485 Connection CE4 Carry out the connections...

Страница 31: ...e the fly lead with an alternative method of connection to the electrical supply 5 7 3 CONNECTING A 230V SUPPLY TO THE APPLIANCE PCB WARNING Isolate the appliance from the electrical supply before car...

Страница 32: ...AND DATE Navigate with the keys to set the values 12 17 ENTER TIME AND DATE TIME DATE USE THE ARROWS TO MODIFY 18 11 2013 Note it is possible to change the TIME and DATE DAYLIGHT SAVINGS TIME setting...

Страница 33: ...tantaneously interrupted 6 2 2 CONFIGURATION OF THE ZONE It is possible to customise the management of the heating zone by accessing the ZONES MANAGER menu Access to menu TECHNICAL INSTALLATION ZONES...

Страница 34: ...N OFF timings for each day of the week operating mode AUTO if necessary the default heating schedule can be changed according to the User s needs Refer to 2 10 TIME SCHEDULE User section for detailed...

Страница 35: ...ot produce a switch off but a reduction parallel translation of the climatic curve on NIGHT level 16 C Also in this case the user can indirectly modify the value of the HEATING setpoint inserting once...

Страница 36: ...alue within the range 40 C 80 5 C for high temperature systems or 20 C 45 C for low temperature systems default is high temperature DHW SET HEATING 6 5 ADJUSTING THE HEATING WATER TEMPERATURE WITH AN...

Страница 37: ...the table on the side Accessing the INFO menu from the main page of the REC10 it is possible to display the TIME FUNC SCREED HEATING value regarding the number of hours since the start of the function...

Страница 38: ...present Reset function In order to reset the boiler s operation in the event of a fault it is necessary to access the fault description screen If the lockout is of a non volatile type that requires a...

Страница 39: ...rm E097 iono alarm E085 combustion fault high CO These are temporary alarms that if they occur several times in an hour they become definitive the last error to occur is displayed and is followed by a...

Страница 40: ...lectronics boards AKM and REC 10 MASTER will require the re programming of these parameters Set SERVICE password Select TECHNICAL COMBUSTION MONITORING AIR PURGING CYCLE PARAMETERS EXHAUST PROBE RESET...

Страница 41: ...f replacement it is necessary to always ensure that it is correctly positioned and to strictly observe the reference shown in the figure detector electrode ionisation sensor flame ignition electrode a...

Страница 42: ...ct the internal components and electrical wiring for any defect or deterioration 4 Visually check for any dirt or debris within the condensate trap the trap is translucent and can be checked visually...

Страница 43: ...nt hysterisis the burner will re light NOTE Ifburnerignitionisnotdetectedatthefirstattempt theappliance will repeat the ignition sequence another two times 3 times in total before going to lockout Whe...

Страница 44: ...continuity 8 7 APPLIANCE STATUS AND FAULT CODES When the boiler detects a temporary fault condition the appropriate code is shown If when the fault is final the pump will perform 30 to 60 second post...

Страница 45: ...iance The UNICA MAX S system boilers incorporate an internal relay that enables a direct switched 230v supply to be used to generate a heating or hot water request from an external control system such...

Страница 46: ...T Pressure transducer MOD Modulator F Lv Fan signal control M GREY BROWN BLUE ORANGE ORANGE BLUE BROWN GREY M N L 230 V Fuse 3 AMP NO NC COM NO NC COM ROOM THERMOSTAT CYLINDER THERMOSTAT M NO NC COM...

Страница 47: ...SC2 blue S E brown yellow green N F X6 3 1 red 24 Vdc yellow B orange A black red 24 Vdc yellow B orange A black REC black orange A yellow B red 24 Vdc A B CE4 removable connector positioned under she...

Страница 48: ...E password 3 Select TECHNICAL COMBUSTION MONITORING GAS TYPE LPG ERROR HISTORY EXHAUST PROBE RESET AIR PURGING CYCLE PARAMETERS COMBUSTION MONITORING SERVICE TECHNICAL BOILER TYPE COMBUSTION OFFSET GA...

Страница 49: ...h section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES I Is s C CO O 3 35 50 0p pp pm m a an nd d C CO O C CO O2 2 r ra at...

Страница 50: ...turers recommendations at least annually This must be carried out by a competent Gas Safe registered engineer The service details should be recorded on the Benchmark Service and Interim Boiler Work Re...

Страница 51: ...no what is the maximum central heating output selected kW Dynamic gas inlet pressure mbar C Central heating return temperature C System correctly balanced rebalanced Yes COMBINATION BOILERS ONLY Is t...

Страница 52: ...eer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas...

Страница 53: ...eer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas...

Страница 54: ...missioning sheet RGII Installation Certificate ROI the warranty will commence from the date of manufacture as detailed on the appliance data plate 6 To qualify for the full term of warranty the boiler...

Страница 55: ...dhered to f To any other costs or expenses caused by or arising as a result of the breakdown of a Vok ra Boiler g To any costs incurred during delays in fixing reported faults 10 We reserve the right...

Страница 56: ...Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the right to change specification without prior notice Consumers statutory rights are not affected Company Reg...

Отзывы: