6. SECTION - COMMISSIONING
NOTE:
please refer to section 4, section 4.1 and use the ap-
propriate PPE when carrying out any of the actions or proce-
dures contained within this section.
6.1 PRELIMINARY CHECKS
Before starting up the boiler, check:
-
confirm via the appliance data badge, that the appliance is
suitable/configured for the gas type and electrical supply
that has been provided to the appliance
-
inspect the entire flue system and ensure that it has been
installed in accordance with these instructions and the
relevant standards that apply locally and/or nationally
- that the required clearances have been met in respect of the
requirements for maintenance
- inspect the entire installation including the gas meter, test
for tightness and purge. Refer to BS 6891 (I.S. 813 in ROI)
for specific instruction
- ensure that the rated delivery of the gas meter is adequate
enough to serve this appliance and any other gas appliance
connected to the same meter
- ensure that the gas supply pipework is of adequate size to
provide the maximum gas rate required by this appliance.
6.1.1 FIRST IGNITION ERRORS
- Ensure that the gas supply is ON, water supply is ON, and
electrical supply is ON. Ensure that the system pressure is
at least 0.6 bar.
- Pump rotator shaft seized (possible alarm code E020 and
no circulation within boiler/heating system); this can occur
if the appliance has been stored or inactive for a prolonged
period.
- To ‘release’ the seized rotator shaft:
- remove front cover as detailed in 5.7.1
- set the boiler to OFF
42
°C
MENU
STATE
SET
INFO
HOT WATER TEMPERATURE
FRI
1.3
bar
09/04/2021
12:17
PLANT
BOILER
MAIN ZONE
STATE
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
- follow in sequence
a-b
b
Perform this operation with extreme caution to avoid
damaging the components.
1
2
1
2
a
b
- replace the front cover as detailed in 5.7.1 ensuring
correct seal.
6.2 PROGRAMMING THE BOILER
- Position the system’s main switch to the “on” position. The
boiler display looks like this:
FRI
09/04/2021
12:17
MENU
INFO
SET
PLANT
HOT WATER TEMPERATURE
STATE
42
°C
1.3 bar
-
In some cases it may be necessary to set the TIME and
DATE; in this case the machine interface request you to
carry out the operation with the message “SET TIME AND
DATE”. Navigate with the keys to set the values.
12
17
:
ENTER TIME AND DATE
TIME & DATE
USE THE ARROWS TO MODIFY
18 / 11 / 2013
-
Note:
it is possible to change the TIME and DATE,
DAYLIGHT SAVINGS TIME settings, as well as LANGUAGE
and the duration of the back-lighting, at any time by entering
the MENU from the main screen and then selecting
SETTINGS.
-
The device automatically manages the change of time from
solar to daylight savings time and vice versa.
b
Whenever the power supply to the appliance is
interrupted and then restored, an automatic venting
cycle is carried out lasting 6 min. To interrupt the vent
cycle, carry out the procedure explained in the section
6.3.
- Set the boiler to OFF from REC10CH selecting STATE
BOILER.
42
°C
MENU
STATE
SET
INFO
HOT WATER TEMPERATURE
FRI
1.3
bar
09/04/2021
12:17
PLANT
BOILER
MAIN ZONE
STATE
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
- Through the REC10CH it is possible to access, using the
TECHNICAL menu, a series of parameters that can be
programmed to allow you to personalise the operation
of the boiler based on the type of system. There are 3
access levels: USER, INSTALLER and SERVICE (see “3.1
Structure of the REC10CH MENU”).
-
Access the parameters and set the operation according to
your type of system.
6.2.1 BOILER CONFIGURATION
The REC10 UI is supplied with a default configuration that
enables a standard type of external control, e.g. room
thermostat & clock, programmable room thermostat, etc. to
be connected to the appliance or alternatively the Vokera
BeSMART OT+ control. Alternatively and if desired the
embedded 7-day clock can be enabled (default is disabled) to
control the ON/OFF time schedule for the central heating. In
order to enable the embedded clock, it is necessary to access
the ‘INSTALLATION’ parameters as defined in
section 8.
NOTE
Do not enable the embedded clock if another type of timing
control, e.g. time clock, programmable room thermostat, etc.
is – or will be – connected to the appliance, in order to manage
the heating timing schedule. The following functions can also
be accessed and adjusted via the installer parameters (see
section 8) if required/necessary.
NOTE
The ‘installer’ parameters should only be accessed and
adjusted by suitably qualified personnel.
- Select PARAMETERS.
TERMOREGOLAZIONE
PARAMETERS
INSTALLATION
WEATHER COMPENSATION
RANGE RATED
TECHNICAL
INSTALLER
CALIBRATION
- Select from among the following options,
confirming the
selection.