INStAllAtION
—
confined locations in which the device's sound levels mi-
ght be compounded by reverberations or resonances
—
proximity to bedrooms and rooms for resting
—
positioning in corners where dust, leaves, or any other
materials typically accumulate, which could compromise
the device efficiency by obstructing the airflow
—
situations in which the air expelled from the device might
enter the habitation through doors or windows, thus cre-
ating an inconvenience for the people inside
—
situations in which the air expelled from the device will
encounter resistance from opposing winds
—
direct exposure to sunlight and proximity to heat sources
9
Avoid placing the unit less than 1 metre away from radio and
video systems.
9
If the unit is installed in a windy location, fit an anti-wind
grille to protect the fan and check the correct functioning of
the unit.
9
Decide where to place the unit considering the length of co-
oling lines and the maximum difference of height allowed
between the devices.
9
2.7
Recommended distances
The distances for the device installation and maintenance are
shown in the figure. The indicated spaces are necessary in order
to prevent the airflow from being blocked, as well as to allow
normal cleaning and maintenance operations to be carried out.
SINGlE INStAllAtIONS
150
300
200
1000
1000