When necessary, the flue gas flange (

A

), must be removed or replaced 

using a screwdriver as a lever.

  In this case, the combustion supporting air is taken from the 

room in which the boiler is installed, which must be a suitable 

and ventilated technical room.

  Non-insulated fumes outlet ducts are potential sources of danger.

  It is appropriate to install a condensate collector and specific 

pipes. In this case realize an inclination of 3° to the condensate 

collector.

24 KIS

Max length fumes

outlet duct Ø 80 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

up to 2m

42

1,2m

1,7m

from 2m to 8m

44 (*)

from 8m to 25m

not installed

28 KIS

Max length fumes

outlet duct Ø 80 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

up to 4m

43

1,2m

1,7m

from 4m to 9m

45 (*)

from 9m to 15m

47

from 15m to 21m

not installed

35 KIS

Max length fumes

outlet duct Ø 80 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

up to 5m

49 (*)

1,2m

1,7m

from 5m to 12m

not installed

(*) fitted in the boiler

“SEALED” INSTALLATION (TYPE C)

The boiler must be connected to concentric or twin fumes discharge 

and air intake ducts which must both be taken outside. Do not use 

the boiler without them.

Concentric outlets (ø 60-100, fig. 10d)

The concentric outlets can be placed in the most suitable direction 

according to room requirements.

For installation, follow the instructions supplied with the kit.

When necessary, the flue gas flange (

A

), must be removed or replaced 

using a screwdriver as a lever.

  It is appropriate to install a condensate collector and specific 

pipes. In this case realize an inclination of 3° to the condensate 

collector.

24 KIS

Max linear length 

concentric

duct Ø 60-100 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

up to 0,85m

42

1,0m

1,5m

from 0,85m to 2,35m

44 (*)

from 2,35m to 4,25m

not installed

28 KIS

Max linear length 

concentric

duct Ø 60-100 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

up to 0,85m

43

1,0m

1,5m

from 0,85m to 1,70m

45 (*)

from 1,70m to 2,70m

47

from 2,70m to 3,40m

not installed

35 KIS

Max linear length 

concentric

duct Ø 60-100 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

up to 0,85m

49 (*)

1,0m

1,5m

from 0,85m to 2,3m

not installed

(*) fitted in the boiler

Concentric outlets (ø 80-125, fig. 10g)

The boiler has been designed to be connected to concentric outlet/

suction pipes and with the opening for air suction closed.

The concentric outlets can be placed in the most suitable direction 

according to room requirements, complying with the maximum lengths 

indicated in the table.

For installation, follow the instructions supplied with the kit.

To go through the wall, drill a hole of Ø 130 mm.

According to the length of the pipes used, it is necessary to insert a 

flange selecting from those contained in the boiler.

Pay special attention to external temperature and pipe length. Refer 

to the diagram (fig. 10h) in order to establish if it is compulsory or not 

to use a condensation collector. In case of operation at temperature 

lower than 60 °C, it is compulsory to use a condensation collector. If 

a condensation collector is used, provide a slope of the flue exhaust 

pipe of 3° towards the collector.

Connect the condensation trap syphon to a white water outlet pipe.

Non insulated outlet pipes are potential sources of danger.

24 KIS

Max linear length 

concentric duct

Ø 80-125 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

from 0,96 to 3,85 m

42

1,35m

2,2m

from 3,85 to 7,85 m

44 (*)

from 7,85 to 12,4 m

not installed

28 KIS

Max linear length 

concentric duct

Ø 80-125 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

from 0,96m to 2,9m

43

1,35m

2,2m

from 2,9m to 5,20m

45 (*)

from 5,20m to 7,10m

47

from 7,10m to 10m

not installed

35 KIS

Max linear length 

concentric duct

Ø 80-125 mm

Flue gas 

flange (ø)

Load losses

45° bend

90° bend

from 0,96m to 2m

49 (*)

1,35m

2,2m

from 2m to 5,85m

not installed

(*) fitted in the boiler

START 24 KIS - reduced concentric bend

86,5

  If it is necessary to install the boiler on systems already existing (replacement 

types Residence KIS), there is a “reduced concentric bend kit” available that 

allows positioning the boiler by keeping the same flue gas hole.

Pipe length with 

reduced bend 

(m)

Flue gas 

flange (A)

Load losses fort esch 

bend (m)

45°

90°

up to 1,85

Ø 44 (**)

1

1,5

from 1,85 to 4,25

not installed

Twin outlets (ø 80, fig. 10e)

Twin outlets can be placed in the most suitable direction according to 

the room requirements.

Remove the closure plug secured with the screws and use the specific 

adaptor for the combustion air intake pipe (

E

).

  The air inlet adaptor ø 80 (

E

) must be correctly directed, it is 

necessary to fasten it with the appropriate screws, so that the 

positioning flap does not interfere with the shell.

When  necessary,  the  flue  gas  flange  (

A

), must be removed using 

a screwdriver as a lever. The table indicates the permitted linear 

lengths. According to the length of the pipes used, it is necessary to 

insert a flange, selecting one from those contained in the boiler (see 

the following table).

Содержание 20122798

Страница 1: ...START 28 KI START 24 28 35 KIS EN INSTALLER AND USER MANUAL FR MANUEL D INSTALLATION ET D UTILISATION...

Страница 2: ...14 30 EU Low voltage directive 2014 35 EU EN Manuel d installation Manuel de l utilisateur 20 32 l ments fonctionnels de la chaudi re 38 Circuit hydraulique 40 Sch mas lectriques 42 Pr valence r sidue...

Страница 3: ...the room close the gas shut off device call the Technical Assistance Service or a professionally qualified technician immediately Do not touch the boiler when barefoot or with any wet parts of the bo...

Страница 4: ...useful head of the pump are suitable for the system the system is washed free of all dirt and build up de aerated and correctly sealed the boiler condensate drain system siphon is connected and route...

Страница 5: ...ation transformer with a secondary circuit connected to the earth The earth wire must be approximately 2 cm longer than the other wires YOU MUST use a general trip switch to disconnect the line in com...

Страница 6: ...ced in the most suitable direction according to room requirements complying with the maximum lengths indicated in the table For installation follow the instructions supplied with the kit To go through...

Страница 7: ...boiler is bled automatically via the automatic air vent valve on the pump Ensure that the valve of the air vent valve is open EMPTYING Before emptying disconnect the electric power supply by switchin...

Страница 8: ...standby until the burner switches on following a heat request The boiler continues to function until the temperatures set on the boiler are reached or the heat request terminates it will then go back...

Страница 9: ...bustion check START KI Install the Flue analysis collection kit in the straight pipe section after the hood output at least 400 500 mm from the hood as envisaged by current standards To install follow...

Страница 10: ...ck to the required setting If there are frequent drops in pressure please request support from the Technical Assistance Service Fault A06 The boiler operates normally but does not guarantee a stable d...

Страница 11: ...y two turns and connect a pressure gauge Disconnect the compensation tube from the air chamber only KIS model Compensation tube Pressure tapping point downstream of gas valve Protection cap Maximum ou...

Страница 12: ...apping point screw JP1 JP2 JP3 JP4 JP5 JP6 CN8 CN7 CN6 CN5 CN12 1 CN13 P1 P3 P2 MP JP2 JP1 To terminate calibration without memorising the set values either a set the function selector to OFF unblock...

Страница 13: ...mbustion chamber cover and the lower shell START KIS combustion chamber cover and air chamber cover Turn the control panel forwards Remove the cover C to access the control board C START KI START KIS...

Страница 14: ...basic safety requirements Do not operate electrical devices or appliances such as switches or domestic appliances etc if you can smell gas or unburned gas Should this occur open the doors and windows...

Страница 15: ...anti clockwise to decrease the value min 37 C max 60 C The boiler remains on standby until the burner ignites following a heat request The boiler operates until the controlled temperatures are reache...

Страница 16: ...please request support from the Technical Assistance Service Fault A04 The digital display shows the fault code together with the symbol Check the pressure shown on the water gauge if the pressure is...

Страница 17: ...Air flow rate Nm3 h 50 960 48 088 49 811 39 613 40 249 40 454 48 052 47 071 48 749 56 894 56 920 Flue flow rate Nm3 h 54 160 50 432 52 285 42 204 41 008 41 455 51 112 49 312 51 114 60 666 59 837 Exce...

Страница 18: ...305 9 Burner number of nozzles n 11 11 11 diameter of nozzles mm 1 35 0 78 0 78 CH maximum gas capacity Sm3 h 2 73 kg h 2 03 2 00 DHW maximum gas capacity Sm3 h 2 73 kg h 2 03 2 00 CH minimum gas capa...

Страница 19: ...inimum pressure mbar 1 60 3 60 4 80 mm H2O 16 32 36 71 48 95 START 35 KIS Supply nominal pressure II2H3P mbar mm H2O 20 203 9 37 377 3 Burner number of nozzles n 16 16 diameter of nozzles mm 1 40 0 80...

Страница 20: ...ls qui emploient des combustibles de l nergie lectrique et de l eau comporte le respect de certaines r gles de s curit fondamentales telles que L utilisation de la chaudi re est interdite aux enfants...

Страница 21: ...etien V rifiez que le degr de protection lectrique de l appareil soit adapt aux caract ristiques du lieu d installation Si les chaudi res sont aliment es avec un gaz combustible de poids sp cifique su...

Страница 22: ...ble d alimentation lectrique d j raccord lectriquement et n cessite seulement du raccordement du des thermostats TA effectuer aux bornes d di es Positionnez l interrupteur g n ral de l installation su...

Страница 23: ...doit tre retir e ou replac e en faisant levier avec un tournevis Il convient d installer un collecteur de condensat et tuyaux sp cifiques Dans ce cas r aliser une inclinaison de 3 vers le collecteur...

Страница 24: ...sur de murs oppos s C82 C82x vacuation dans un conduit de fum es unique ou com mun et aspiration murale C92 C92x vacuation au toit similaire C32 et aspiration d air depuis un conduit de fum es unique...

Страница 25: ...la demande en cours Lors de l allumage du br leur suite une demande de pr chauffage l afficheur montre le symbole clignotant Pour d sactiver la fonction pr chauffage tourner nouveau la poign e de r g...

Страница 26: ...e Tournez le panneau de commande en avant START 24 KIS B B B START 28 KI 28 KIS START 35 KIS D vissez de deux tours environ la vis de la prise de pression situ e en amont de la soupape du gaz et racco...

Страница 27: ...06 Signalisation Panne NTC chauffage A07 Arr t temporaire Surchauffe sonde refoulement chauffage Temporaire puis d finitif Alarme diff rentielle sonde refoulement retour Blocage d finitif Flamme paras...

Страница 28: ...les prestations de la chaudi re selon les sp cifications relatives Toute cause de d t rioration visible doit imm diatement tre identifi e et limin e Rechercher minutieusement sur la chaudi re tout dom...

Страница 29: ...s lecteur de fonction en tat hiver sans de demande de chaleur en cours L activation de la fonction pr voit l allumage du br leur travers la simulation d une demande de chaleur en chauffage Pour effect...

Страница 30: ...aphe sp cifique et appliquez la nouvelle plaque signal tique contenue dans le kit START 24 28 35 KIS START 28 KI En cas de transformation du gaz M thane GPL proc dez comme il est d crit ci dessous Cou...

Страница 31: ...d j pr sent Remontez l enveloppe 4 10 Nettoyage de la chaudi re Avant toute op ration de nettoyage coupez l alimentation lectrique en mettant l interrupteur g n ral de l installation sur teint Nettoya...

Страница 32: ...t fondamentales telles que Il est interdit d actionner des dispositifs ou des appareils lec triques tels que des interrupteurs des lectrom nagers etc si vous sentez une odeur de combustible ou de gaz...

Страница 33: ...ur dans le sens antihoraire pour la diminuer valeur min 37 C valeur max 60 C La chaudi re est dans un tat de stand by jusqu ce que suite une demande de chaleur le br leur s allume La chaudi re restera...

Страница 34: ...de l anomalie ainsi que le sym bole V rifiez la valeur de pression indiqu e par l hydrom tre si elle est inf rieure 0 3 bar positionnez le s lecteur de fonction sur teint OFF et agissez sur le robine...

Страница 35: ...bit des fum es Nm3 h 54 160 50 432 52 285 42 204 41 008 41 455 51 112 49 312 51 114 60 666 59 837 Indice exc s d air puissance maximale 1 668 1 653 1 687 1 608 1 715 1 699 1 645 1 692 1 727 1 580 1 6...

Страница 36: ...kg h 2 51 2 48 D bit gaz maximum sanitaire Sm3 h 3 37 kg h 2 51 2 48 D bit gaz minimum chauffage Sm3 h 1 48 kg h 1 10 1 09 D bit gaz minimum sanitaire Sm3 h 0 92 kg h 0 69 0 68 Pression maximum en ch...

Страница 37: ...mbar 1 60 3 60 4 80 mm H2O 16 32 36 71 48 95 START 35 KIS Pression nominale d alimentation II2H3P mbar mm H2O 20 203 9 37 377 3 Br leur nombre de buses n 16 16 diam tre des buses mm 1 40 0 80 D bit ga...

Страница 38: ...START KI KIS 38 START 28 KI START 24 KIS 10 3 10 3...

Страница 39: ...tion 18 Pompe de circulation 19 Interrupteur de flux 20 Vanne trois voies 21 changeur sanitaire 22 Thermostat fum es uniquement mod le KI EN Boiler functional elements 1 Filling tap 2 Discharge valve...

Страница 40: ...n tank 14 Air vent valve 15 Circulator 16 Three way solenoid 17 Flow regulator 18 Domestic hot water flow switch 19 DHW filter FR Circuit hydraulique AF Entr e sanitaire AC Sortie sanitaire G Gaz M Re...

Страница 41: ...r Heating domestic hot water temperature or operation faults FR Panneau de commande 1 Hydrom tre 2 Afficheur num rique qui signale la temp rature de fonctionnement et les codes d anomalie 3 S lecteur...

Страница 42: ...A1 MP C 3V 2 N 1 sanit 3 risc nero sanit marrone risc blu 3 1 CN4 7 1 CN9 blu marrone T F 1 4 CN10 nero nero marrone marrone T L S R t 1 12 CN11 F L viola viola rosso rosso t S S bianco bianco P A 2 3...

Страница 43: ...1 sanit 3 risc nero sanit marrone risc blu 3 1 CN4 7 1 CN9 grigio grigio 3 1 P F nero marrone CN3 blu V 1 2 1 4 CN10 nero nero marrone marrone T L S R t 1 12 CN11 F L viola viola rosso rosso t S S bia...

Страница 44: ...NTC T L Limit thermostat OPE Gas valve operator P Pump 3V Servomotore valvola 3 vie F L Domestic hot water flow switch S S Domestic hot water circuit temperature probe NTC PA Heating pressure switch...

Страница 45: ...position The antiblocking function is active only if the boiler is electri cally powered Operating the circulator without water is strictly forbidden FR Pr valence r siduelle du circulateur A Pr vale...

Страница 46: ...START KI KIS 46 200 mm 1 3 2 50 mm 50 mm START KI START KIS START KIS 3a...

Страница 47: ...START KI KIS 47 5 4 START KI START KIS START 28 KI 28 KIS START 24 KIS M M M AC AC AC G G G R R R AF AF AF START 35 KIS...

Страница 48: ...START KI KIS 48 7 6 START 28 KI 28 KIS START 24 KIS A A B B B A START 35 KIS START 24 KIS START 28 KI 28 KIS START 35 KIS...

Страница 49: ...C52 C32 C32 C92 C82 C22 C22 C42 C42 B22 C12 C12 C52 A A rear outlet sortie arri re B max 50 cm max 50 cm B START KIS 10b START 24 KIS START 28 KIS START 35 KIS C22 only 24 KIS model uniquement mod le...

Страница 50: ...KIS START 35 KIS 10c A A CONCENTRIC OUTLETS 60 100 CONDUITS CONCENTRIQUES 60 100 10d A A A A 60 80mm adaptor adaptateur 60 80mm 60 80mm adaptor adaptateur 60 80mm 60 80mm adaptor adaptateur 60 80mm S...

Страница 51: ...START KI KIS 51 E E E A A A TWIN OUTLETS 80 CONDUITS DEDOUBLEES 80 10e START 24 KIS START 28 KIS START 35 KIS...

Страница 52: ...gth of flue pipe m longueur conduit vacuation fum es m air intake pipe length m longueur conduit aspiration air m fumes flange 44 bride fum es 44 no fumes flange bride fum es non install e no fumes fl...

Страница 53: ...re la plus adapt e l installation entr e d air droite 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 7 5 8 0 8 5 9 0 9 5 10 0 10 5 11 0 11 5 12 0 12 5 13 0 13 5 14 0 30 25 20 15 10 5 0 5...

Страница 54: ......

Страница 55: ......

Страница 56: ...Cod 20124760 03 17 Ed 3...

Отзывы: