20173117
38
GB
Start-up, calibration and operation of the burner
6.8
Description of O
2
trim control (optional)
A special feature of the LMV52… is control of the residual O
2
content to increase the boiler’s efficiency. The LMV52… uses a
QGO20…, an external PLL52…, and the standard components
of the LMV51… The PLL52… is a detached measuring module
for the O
2
sensor and for 2 temperature sensors (Pt1000 / LG-
Ni1000). The module communicates with the LMV52… via CAN
bus.
The following generic diagram shows the system
6.8.1
Operating principle of O
2
trim control
The residual O
2
control system reduces the amount of combu-
stion air depending on the control deviation (O
2
setpoint minus
actual of O
2
). The amount of combustion air is normally influen-
ced by several actuators and, if used, by a VSD.
Reduction of
the amount of air is reached by reducing the «air rate» of the
air-regulating actuators.
For that purpose, the damper positions of these actuators are cal-
culated from some other load point on the ratio control curves.
Hence, due to the parameterized ratio control curves, the air-re-
gulating actuators are in a fixed relation to one another.
O
2
trim control is supported by
precontrol. Precontrol calcula-
tes the air rate reduction such that changes in burner load
do not require the O
2
trim controller to interfere.
Considera-
tion is given to a number of measured values that are ascertained
when the burner is set. This means that the controller only beco-
mes active when environmental conditions (temperature, pressu-
re) change, and not when the burner load changes.
Fig. 33
S9903
QGO20...
Flue gas
sensor
temperature
O
2
module PLL...
CAN
Sensor of
Combustion air
LMV52...
Temperature
WARNING
The installation and setting of the system must be
carried out by qualified personnel, as indicated in
the specific documentation of the device.
Содержание 1135T1
Страница 2: ...Translation of the original instructions...
Страница 29: ...27 20173117 GB Installation Fig 20 No Setpoint air gas Max burner output kW 20081480...
Страница 53: ...51 20169327 GB Appendix Electrical panel layout ALL MODELS RS 310 RS 410 DIRECT START UP...
Страница 54: ...20169327 52 GB Appendix Electrical panel layout RS 310 RS 610 STAR TRIANGLE START UP...
Страница 57: ...55 20169327 GB Appendix Electrical panel layout ALL MODELS...
Страница 58: ...20169327 56 GB Appendix Electrical panel layout ALL MODELS...
Страница 59: ...57 20169327 GB Appendix Electrical panel layout 0 ALL MODELS...
Страница 60: ...20169327 58 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ALL MODELS...
Страница 61: ...59 20169327 GB Appendix Electrical panel layout 0 1 1 1 2 ALL MODELS...
Страница 66: ...20169327 64 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3 ALL MODELS...