9
20173117
GB
Technical description of the burner
Tab. E
STAR - TRIANGLE START UP
Model
RS 410/E O
2
BLU
RS 510/E O
2
BLU
RS 610/E O
2
BLU
Main electrical supply
3N ~ 400V +/-10% 50 Hz
Fan motor IE2
rpm
V
kW
A
2930
400/690
9,2
16,5/9,6
2880
400/690
12
21,3/12,3
2915
400/690
15
26,8/15,5
Ignition transformer
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
Absorbed electrical power
kW max
10,8
13,7
17
Protection level
IP 54
WARNING
The burner leaves the factory set to operate
FS1. When required operation FS2, see speci-
fic manual LMV5...