Technical description of the burner
4.7
Firing rates
The
MAXIMUM OUTPUT
is chosen from within the diagram area
(Fig. 2).
The
MINIMUM OUTPUT
must not be lower than the minimum
limit of the diagram:
Tab. G
Model
kW
RS 310/E O
2
BLU
400
RS 410/E O
2
BLU
500
RS 510/E O
2
BLU
680
RS 610/E O
2
BLU
1000
WARNING
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
shown on pag. 26.
Thermal power –
kW
Co
mb
ustion chamb
er
combustion
h
ead
-
mba
r
Fig. 2
400
800
1200
1600
2000
2400
2800
3200
3600
4000
4400
4800
0
2
4
6
8
10
12
14
16
18
5200
5600
6000
6400
6800
-2
20
20058566
RS 310/E
RS 410/E
RS 510/E
RS 610/E
Содержание 1135T1
Страница 2: ...Translation of the original instructions...
Страница 29: ...27 20173117 GB Installation Fig 20 No Setpoint air gas Max burner output kW 20081480...
Страница 53: ...51 20169327 GB Appendix Electrical panel layout ALL MODELS RS 310 RS 410 DIRECT START UP...
Страница 54: ...20169327 52 GB Appendix Electrical panel layout RS 310 RS 610 STAR TRIANGLE START UP...
Страница 57: ...55 20169327 GB Appendix Electrical panel layout ALL MODELS...
Страница 58: ...20169327 56 GB Appendix Electrical panel layout ALL MODELS...
Страница 59: ...57 20169327 GB Appendix Electrical panel layout 0 ALL MODELS...
Страница 60: ...20169327 58 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ALL MODELS...
Страница 61: ...59 20169327 GB Appendix Electrical panel layout 0 1 1 1 2 ALL MODELS...
Страница 66: ...20169327 64 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3 ALL MODELS...