● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the numbers of the
battery pack, please make sure you modify the setting simultaneously. The connection with wrong battery voltage may
cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
● Pay highly attention to the polarity marking on external battery terminal block, and make sure the correct battery polarity
is connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The wire current spec, color, position, connection and
conductance reliability should be checked carefully.
● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection and conductance
reliability should be checked carefully. Make sure the L/N site is correct, not reverse and short-circuited.
TRANSFORMER
BOX
E
LECTRICAL
I
NSTALLATION
Output of the UPS should be connected to the input of transformer box and the output of transformer box
is the final output of system.
Follow below diagram to connect UPS output to Input of transformer box.
240V Input
208V Input
Confirm the UPS output voltage through the front panel and verify that it matches the
transformer box
output voltage.
For example, if the input to UPS is 208V, then voltage selection should be 208V.