29
⚫
4
: ECO enable/disable
Interface
Description and Possible configurations
Parameter:
Enable or disable ECO function. You may choose the following
two options:
⚫
ENA:
ECO mode enable
⚫
DIS:
ECO mode disable (Default)
⚫
5
: Bypass enable/disable when UPS is off
Interface
Description and Possible configurations
Enable or disable Bypass function. You may choose the following two
options:
⚫
ENA:
Bypass enable
⚫
DIS:
Bypass disable (Default)
⚫
6
: Reserved
Interface
Description and Possible configurations
Reserved
⚫
7
: Reserved
Interface
Description and Possible configurations
Reserved
⚫
8
: Autonomy limitation setting
Interface
Description and Possible configurations
Parameter 2:
Set up backup time on battery mode for
000~999:
Set the
maximum backup time from 0min to 999min. UPS will shut down to
protect battery after backup time arrives.
DIS:
Disable battery discharge protection and backup time will depend on
battery capacity.
The default value is DIS.
⚫
9
: Battery total AH setting
Interface
Description and Possible configurations
Parameter 2:
Set up the battery AH of the UPS .
7-200:
setting the battery capacity from 7-200 in AH(1 PCS).
Please set the correct battery total capacity if external battery pack is
connected.