NSTALLATION ENVIRONMENT
The UPS, the Battery Pack and the Transformer Box must be installed in ventilated, clean environments which are
sheltered from bad weather.
The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table.
The ambient temperature, whilst the UPS is in operation, must remain between 0 and 40°C, and the UPS must not be
positioned in places which are exposed to direct sunlight or to hot air.
The recommended operating temperature for the UPS and the batteries is between 20 and 25°C. The actual
operating life of the batteries is 5 years on average with an operating temperature of 20°C. If the operating
temperature reaches 30°C, the operating life is halved.
This is a category
C3 UPS product. In a commercial and industrial application in the second environment-
installation restrictions or additional measures may be needed to prevent disturbances.
B
ATTERY PACK INSTALLATION
ATTENTION:
CHECK ON THE DATA PLATE THAT THE VOLTAGE OF THE BATTERY PACK IS THE SAME AS THAT
ALLOWED BY THE UPS.
N
ON
-ER
M
ODEL
The standard 6kVA/10kVA UPS is only allowed to connect
ONE
battery pack. Simply use one battery cable to connect
UPS and battery pack as below chart.
Non-ER Model
Battery Pack