30
⚫
10
: Setting charge current
Interface
Description and Possible configurations
Parameter 2:
Set up charging current of the charger
001~004.
CAUTION: This setting is only available for ER models. NEVER
change this setting for standard models.
Set the charging current of the charger from 1A to 4A.
⚫
11
: Fine-turning charge current
Interface
Description and Possible configurations
Parameter 2:
Fine-turning charge current
± 0~± 5:
you may choose
‘+’
as
add
or
‘-‘
as
Sub
to adjust charging
current
+ 1:
Charging current will increase about 0.01A.
- 1:
Charging current will decrease about 0.01A.
⚫
0
: Exit setting
Interface
Description
Exit the setting mode.
A
DDITIONAL FUNCTIONS
MANUAL BYPASS
Using the Manual Bypass feature, the UPS can be switched to bypass. In this condition the load is powered directly by the
input mains, any disruption in the mains directly affects the load.
CAUTION:
BEFORE CARRYING OUT THE FOLLOWING SEQUENCE OF OPERATIONS, ENSURE THAT THE UPS’S
INPUT AND OUTPUT FREQUENCY COINCIDE AND THAT THE UPS IS NOT OPERATING FROM THE
BATTERY
Attention: even when the UPS is switched on, the load is disconnected in the event of a mains blackout.
If the input mains deviates from the established tolerances, the UPS automatically switches to STANDBY mode and
disconnects the load.
To force the UPS into manual bypass mode, press and hold down the ON/MUTE and SELECT keys simultaneously for at
least 4 seconds.
The code "C02" appears on the display.
To return to the normal operation mode press the ON/MUTE and SELECT keys again for at least 4 sec.