Rich Electric Co. “SuperCombi” User Manual V7.19 Copyright 2009
Page 154
The absorption voltage has
been set to an incorrect
value.
Adjust the absorption
voltage to the correct value.
The battery is overcharged.
The float voltage has been
set to an incorrect value.
Adjust the float voltage to
the correct value.
The battery is too small.
Reduce the charging current
or use a battery with a higher
capacity.
A defective battery.
Replace the battery.
The battery is overcharged.
The battery is too hot.
Connect a Battery
Temperature Sensor (BTS-3)
Battery over temperature
(
>
50
℃
)
1. Allow battery to cool
Down.
2. Place battery in a cool
Environment.
3. Check for shorted cells.
Battery charge current drop
to 0 A when the absorption
voltage is reached.
Battery Temperature Sensor
(BTS-3) is faulty
1.
Unplug Battery
Temperature Sensor
(BTS-3) from
“SuperCombi®”
and power
off the “SuperCombi®”
then wait 5 seconds and
Power on again.
2.
If the “SuperCombi®”
AC CHARGE normally,
the BTS-3 is faulty and
needs to be replaced.
Содержание Invertek SuperCombi SC-1500-12X
Страница 1: ......
Страница 2: ...Rich Electric Co SuperCombi User Manual V7 19 Copyright 2009 Page 2...
Страница 9: ...Rich Electric Co SuperCombi User Manual V7 19 Copyright 2009 Page 9 Layout...
Страница 125: ...Rich Electric Co SuperCombi User Manual V7 19 Copyright 2009 Page 125 Chapter 8 Constants list...
Страница 155: ...Rich Electric Co SuperCombi User Manual V7 19 Copyright 2009 Page 155 NOTES...