Rich Electric Co. “CombiPlus” User Manual V7.19 Copyright 2009
Page 21
Inverter AC Input
CombiPlus®
MCB/RCD
MIN AC Cable Size
single Twin
‐
core and earth
Model
MAX Circuit Breaker Current
Enclosed conduit
Unenclosed free air
1500watt 16Amp
2.5mm 1.5mm
3000watt 32Amp
6mm 4mm
6000watt 63Amp
16mm 10mm
Inverter AC Output
CombiPlus®
MCB/RCD
MIN AC Cable Size
single Twin
‐
core and earth
Model
MAX Circuit Breaker Current
Enclosed conduit
Unenclosed free air
1500watt 25Amp
4mm 2.5mm
3000watt 50Amp
16mm 10mm
6000watt 100Amp
35mm 25mm
THE OUTPUT VOLTAGE FROM THE INVERTER IS LETHAL
For your safety ensure that all installations meet and comply with the relevant
requirements of AS3000 wiring standards and
AC wiring is installed by a Licensed Electrical Contractor.
MAKE SURE THE COMBIPLUS IS SWITCHED OFF AND DISCONECTED FROM ALL
AC AND DC SUPPLIES BEFORE WORKING ON THE SYSTEM!