Setpoints
63
DIGOUT
bit_number
Lists all digital output bits available for the specified SLOT. This parameter is used to
specify the digital output bit associated with this setpoint.
For continuous setpoints, the digital output becomes active (low) when the condition
is met; for batch setpoints, the digital output is active
until
the setpoint condition is
met.
BRANCH
0
1-100
Specifies the setpoint number to which the batch sequence is to branch if the
current setpoint is not satisfied upon initial evaluation.
The special value zero indicates that no branch is taken.
TIME
time
For TOD setpoints, specifies the time at which the setpoint becomes active. The
format used to enter the time (12-hour or 24-hour) is based on the value specified for
the TIMEFMT parameter on the FEATURE menu.
DURATION
hh:mm:ss
For TOD setpoints, specifies the length of time that the digital output associated with
this setpoint changes state. The value is entered in hours, minutes, and seconds
(
hh:mm:ss
). All other operations associated with this setpoint (print, tare, or
accumulate) are performed at the end of the specified duration.
NSAMPLE
1–65535
For AVG setpoints, specify the number of A/D samples used to calculate the average
weight.
SOURCE
source_scale
Specify the scale number used as the source for the setpoint.
DIN SLOT
slot_number
For DIGIN setpoints, specify the slot number from which digital inputs will be read.
DIN MASK
digital_input_mask
For DIGIN setpoints, specify the bits used as inputs to the setpoint. Use the
Select
softkey to select bits.
VUNDER
0–9999999
For CHKWEI setpoints, specifies the lower weight limit.
VOVER
0–9999999
For CHKWEI setpoints, specifies the upper weight limit.
DUNDER
digital_output
For CHKWEI setpoints, specifies the bit number of digital output activated when the
scale weight is less than the VUNDER value specified.
DACCEPT
digital_output
For CHKWEI setpoints, specifies the bit number of digital output activated when the
scale weight between the VUNDER and VOVER values specified.
DOVER
digital_output
For CHKWEI setpoints, specifies the bit number of digital output activated when the
scale weight is greater than the VOVER value specified.
COAST
0–65535
For PLSCNT setpoints,
SETPTS Menu
Parameter
Choices
Description
Table 8-2. Setpoint Menu Parameters (Continued)