25
Installer/Service Menu – Heat/Cool Configuration
Table G. Installer/Service Menu — Heat/Cool Configuration
Item
Range
Default
Value
Access
Level
Description
Set Current
Time
12:00A–11:59P
Installer Selects current time – “A” or “P” will indicate
whether the set time is AM or PM.
Remote
Pool
Heat, Cool, Auto
Cool
Installer Selects unit operation when controlled by
remote.
Pump
Periods
0–4
Installer
Only available if Pump Operation in the
Installer’s Menu is set to “4-Speed Enabled” or
“Variable Enabled”.
Pump On Time 1 12:00A–11:59P
Installer Select ON time for Pump Period #1 to take
effect.
Pump Off Time 1 12:00A–11:59P
Installer Select OFF time for Pump Period #1 to stop.
Pump Speed 1
1–4 if 4-Speed
Enabled
0%–100% if Variable
Enabled
Installer
On 4-speed pumps, this denotes the selected
pump output (which connects to the pump for
the selected speed) for this pump period. On
variable-speed pumps, this denotes the PWM
signal to be provided to the pump for pump
operation.
Return Valve 1
Pool/Spa
Pool
Installer
Select the position of a 3-way valve located
between the heater and the Pool/Spa for this
scheduled pump period.
Suction Valve 1
Pool/Spa
Pool
Installer
Select the position of the 3-way valve located
between the Pool/Spa and the Pump for this
scheduled pump period.
Pump On Time 2 12:00A–11:59P
Installer Select ON time for Pump Period #2 to take
effect.
Pump Off Time 2 12:00A–11:59P
Installer Select OFF time for Pump Period #2 to stop.
Pump Speed 2
1–4 if 4-Speed
Enabled
0%–100% if Variable
Enabled
Installer
On 4-speed pumps, this denotes the selected
pump output (which connects to the pump for
the selected speed) for this pump period. On
variable-speed pumps, this denotes the PWM
signal to be provided to the pump for pump
operation.
Return Valve 2
Pool/Spa
Pool
Installer
Select the position of a 3-way valve located
between the heater and the Pool/Spa for this
scheduled pump period.
Suction Valve 2
Pool/Spa
Pool
Installer
Select the position of the 3-way valve located
between the Pool/Spa and the Pump for this
scheduled pump period.
Pump On Time 3 12:00A–11:59P
Installer Select ON time for Pump Period #3 to take
effect.
(Continued on next page)
NOTE:
Make sure that the values for each setting are recorded for future reference or if the control ever needs to be
reset to Factory Defaults. All these values will need to be re-entered.
Содержание Raypak 2450
Страница 43: ...43 Figure 15 Piping for Heat Pump Pool Heater and Gas Pool Heater...
Страница 52: ...52 NOTES...
Страница 53: ...53 NOTES...