24
Item
Range
Default
Value
Access
Level
Description
AUX1 On Time
12:00A-11:59P
Installer/
Service
Sub-
menu
Select ON time for AUX1 to take effect.
AUX1 Off Time
12:00A-11:59P
Installer/
Service
Sub-
menu
Select OFF time for AUX1 to stop.
AUX2 On Time
12:00A-11:59P
Installer/
Service
Sub-
menu
Select ON time for AUX2 to take effect.
AUX2 Off Time
12:00A-11:59P
Installer/
Service
Sub-
menu
Select OFF time for AUX2 to stop.
Defrost Temp
20°F–35°F
(-6.5°C–1.5°C)
35°F
(1.5°C)
Installer/
Service
Sub-
menu
This is the temperature measured on the coil
when the control goes into Defrost mode.
Def Terminate
40°F–60°F
( 4°C–15.5vC)
50°F
(10°C)
Installer/
Service
Sub-
menu
If the coil temperature reaches this setpoint,
Defrost will terminate. Other Defrost
algorithms are still operating behinds the
scene.
Outside Lockout
Off,
30°F–50°F
(-1°C–10°C)
Off
Installer/
Service
Sub-
menu
The installer can program the control to Lock
out operation of the unit if a specific outside
temperature is measured. Off allows operation
at any ambient temperature.
Set Model Type
HEAT ONLY,
POWER DEFROST,
HEAT/COOL
HEAT/
COOL
Installer/
Service
Sub-
menu
Set at the factory. Will need to be set by
Installer during any replacement of the control
board.
EXV
Disabled, Type 1,
Type 2
Disabled
Installer/
Service
Sub-
menu
Set at the factory on new units. Select
“Disabled” if unit equipped with TXV for board
replacement. EXV Type 1 is 500 step EXV.
EXV Type 2 is 1600 step EXV.
Change EXV to
Yes/No
Installer/
Service
Sub-
menu
This screen asks if you really want to change
the EXV setting – the UP or DOWN button
must be pressed to show YES before the EXV
type will be changed.
Brownout
Detection On
On/Off
On
Installer/
Service
Sub-
menu
This function will shut down operation of the
unit if the 24VAC signal drops below 18VAC to
protect the unit from Low Voltage. This feature
can be turned off as desired.
Set Factory
Defaults
Installer/
Service
Sub-
menu
Press and hold both the UP and DOWN
buttons for 3+ seconds to reset the factory
defaults in the control. When reset, the screen
will display “Defaults Set”.
Содержание Raypak 2450
Страница 43: ...43 Figure 15 Piping for Heat Pump Pool Heater and Gas Pool Heater...
Страница 52: ...52 NOTES...
Страница 53: ...53 NOTES...