Test
- when the system is armed, any detector on the zone
will generate an entry in the Event-Log without
initiating an alarm condition.
Note:
Personal Attack, 24-hour Intruder and Fire
modes all operate on a 24 hour basis, (i.e. they are able
to initiate Full Alarm condition at any time irrespective
of whether the system is Armed or Disarmed).
Default setting: ‘Intruder’
Scroll through the menu until
‘3-2 Z01 Type’
is
displayed. The current setting will also be displayed.
To change the setting press .
Scroll through available options until the required
setting is displayed.
Press to save and exit, or
Press to exit without saving.
Final Exit Set
If enabled, triggering of any detector on the zone
during the exit-delay will cancel any remaining exit-
delay and cause the system to arm 5 seconds later.
Default setting: OFF
Scroll through the menu until
‘3-3 Z01 Final Exit Set’
is
displayed. The current setting will also be displayed.
To change the setting press .
Press to enable the zone’s Final Exit Set
facility, or
Press to disable the zone’s Final Exit Set
facility.
Chime
This controls whether the Chime facility is available on
the zone.
Default setting: OFF
Scroll through the menu until
‘3-4 Z01 Chime’
is
displayed. The current setting will also be displayed.
To change the setting press .
Press to enable the zone’s Chime facility, or
Press to disable the zone’s Chime facility.
Entry Delay
Scroll through the menu until
‘3-5 ENTRY DELAY’
is
displayed. The current settings will also be displayed.
To change the settings press .
On/Off Status
Default setting: zone 1: ON
zones 2-10: OFF
Scroll through the menu until
‘3-5-1 Status’
is
displayed. The current setting will also be displayed.
To change the settings press .
Press to enable the zone’s entry-delay, or
Press to disable the zone’s entry-delay.
Delay Period
Default setting: 30 seconds
Scroll through the menu until
‘3-5-2 Delay Time’
is
displayed.
To change the settings press .
Enter the required delay period (10 to 250s).
Press to save and exit, or
Press to exit without saving.
Press to return to top level Zone Setup.
Part-Arm 1
This controls whether the zone is active when Part-
Arm 1 is armed.
Default setting: OFF
Scroll through the menu until
‘3-6 Z01 Part-Arm 1’
is
displayed. The current setting will also be displayed.
To change the setting press .
Press to enable the Zone in Part-Arm 1, or
Press to disable the Zone in Part-Arm 1.
27
ESC
ESC
ESC
1
3
1
3
1
3
1
3