7.
DIP4 of SW3 is used to set the PIR Detector for
walk test mode, which allows the operation of the
Detector to be checked during installation without
triggering a Full Alarm.
ON Walk Test mode
OFF Normal operation
Note: On initial installation the PIR Detector should
be set into Walk Test mode ready for testing.
8.
The PIR Detector incorporates a sensitivity feature
designed to compensate for situations where the
Detector may be affected by environmental
changes, (e.g. insects, air temperature, etc). This
feature is called “Detection Sensitivity” and may be
set to Standard or High Sensitivity.
Note: The higher the sensitivity the less movement
will be necessary before the PIR Detector will
trigger the alarm.
The recommended setting is Standard Sensitivity.
If set to High Sensitivity, in some cases, extreme
environmental problems could cause unattributed
false alarms. If this is experienced it may be necessary
to reset the PIR Detector to Standard Sensitivity.
Set the required detection sensitivity using DIP 5 of
SW3 as follows:
9.
Connect the PP3 Alkaline battery to the battery clip.
Note: When the 9V Alkaline battery is connected
the LED behind the lens will rapidly flash for
approximately 2-3 minutes until the PIR Detector
has warmed up and stabilized. The LED will then
stop flashing and turn OFF.
10. Check that the PIR Detector PCB is located and set
in the correct position to give the detection zone
pattern required.
To adjust the PCB position, simply slide it up or
down ensuring that the location legs are aligned with
the required position number marked on the board.
11. Refit the PIR Detector to the rear cover by offering
the PIR Detector up to the rear cover and locate
the clips in the top edge into the rear cover. Push
the lower edge of the PIR Detector into place and
refit the fixing screw in the bottom edge of the PIR
Detector to secure in position. Do not over-tighten
the fixing screws as this may damage the casing.
Testing the PIR Detectors
Ensure that the Control Panel is in Test mode.
With the PIR detector set in Test mode (i.e. Dip 4 on
SW3 ON) and mounted in position on the wall, allow
2-3 minutes for the detector to stabilize before
commencing the Walk Test.
1.
Use the and buttons to scroll through
the menu until
‘WALK TEST’
is displayed.
Press to activate Walk Test.
‘Walk Test Waiting…’
will be displayed.
2.
Walk into and move slowly around the protected
area, each time the detector senses movement
the LED behind the lens will flash. In addition,
the Control Panel will beep to indicate that the
alarm signal has been received and the identity
of the zone that the detector is configured for
will be displayed.
8
7
6
5
4
3
2
1
2
1
4
3
5
EC
E
EC
E
ON
ON
SW
3
SW
2
5
4
3
2
1
PCB Positions
Indicator
(positions 1-5)
5
4
3
2
1
13
OFF
Standard Sensitivity
ON
High Sensitivity
PCB Position
Range
1
6m
3
9m
5
12m
DIP 4
Mode Trigger reaction
of SW3
on LED
ON
Walk • LED single flash
Test when movement
detected: implies
the sensor is set to
high sensitivity
• LED flashes three
times and illuminates
once: implies the
sensor is set to low
sensitivity
OFF
Normal LED will not light up
Position (unless the battery in
the PIR is low)