REOVIB MFS 268 UL/CSA
Operating Instructions
28
ELEKTRONIK
A 1.0 Service appendix
ATTENTION !
The settings described in this section relating to the service menu are intended for use by skilled
persons because the functions and limits of the feed system can be greatly influenced by their
adjustment
It is the responsibility of the supplier of the equipment to decide whether this information should
be released or restricted for use by service engineers only.
The service menu cannot be accessed through the normal menu structure. It can only be enabled by
using a special key code.
Service Menu
The critical parameters, current limit and user adjustable frequency range are held in a separate service
menu. This menu cannot be reached through the normal menu structure and must be enabled by using
an additional code number. This prevents the unauthorised changing of these sensitive parameters
•
Current Limit – Protects the coil against overload.
The output current limit is set to the maximum current rating of the coil.
•
Frequency limits – Protection against unhealthy operation.
The vibrating frequency limits available to the user are fixed.
•
Output voltage limit 100 V
The output voltage limit allows 110v coils to be used on a 230V supply without damage.
Parameter:
Display
Factory
setting:
Entry code:
•
Enable service menu
0 / I
En.S:
0
127
•
Adjust current limit
0...100 %
I.
100
040
•
Set lower frequency
5...300 Hz
F.L.
35
040
•
Set upper frequency
6...300 Hz
F.H.
140
040
•
Limit output voltage 100 V
0 / I
P.Li.
0
040