REOVIB MFS 268 UL/CSA
Operating Instructions
19
ELEKTRONIK
11.0 Error messages / ERROR reset
Errors are indicated by an alternating code and ERROR display
Overload limit
Output level exceeded e.g. incorrect frequency setting, coil air-
gap to wide.
Short circuit trip
Faulty coil, short circuit or defective cable..
Over voltage
Supply voltage too high or back EMF from the coil at lower fre-
quencies.
Current spike limit
Frequency set too low for installed coil or frequency altered too
rapidly during setting up.
Sensor fault (only when regulation mode is selected)
Accelerometer not working or faulty.
ERROR Reset through Menu C009
Sensor time out
After sensor time out has elapsed
ERROR Reset is achieved by pressing touch panel keys 0 or I during normal operation or by using
Menu C009.
In the event of an error check that this is not caused by incorrect wiring or cable faults. The error mes-
sage, ERROR ACC, can also occur if regulation mode is chosen (in Menu C008) and an accelerometer is
not connected, for example.
Reset the error in the following manner:
ERROR RESET
Frequently appearing Errors, which are not described in this chapter, should be reported to the
manufacturer.
P
P
Clear Error