10.2.6.6 Optimisating controller in regulation mode
Setting the control range
1. In Menu C. 096 set parameter P (Max Limit) to 50 %
2. Set A (Feeder throughput) to 100%
3. Increase limit P from 50% until the required maximum feeder throughput is achieved
The full set point adjustment range of 0…100% can now be used
Optimising regulation: For unwanted feeder oscillation (hunting) or inadequate feedback regula-
tion for load changes
The response of the regulation circuit can be adjusted in menu C008 using the parameter PA (Propor-
tional characteristic or circuit gain) and IA (Integral characteristic)
In menu C008 reduce PA until the oscillations are reduced
Parameter IA should be set to at 100 if possible
10.2.6.7 Displays
1. The maximum output power of the controller has been reached.
The feedback signal from the sensor (acceleration) is too low in com-
parison with the set point. Reduce parameter P in Menu C096 or
C008.
2. The maximum current setting has been reached.
The feedback signal from the sensor (acceleration) is too high.
Changing display:
The regulator oscillates too quickly.
Reduce parameter PA in Menu C008.