SHIPPING, RIGGING, LIFTING AND ASSEMBLY: LE MODELS

19

 

1.800.627.4499 

INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

RENEWAIRE.COM 

CURB DIMENSIONS

5.3 LE10XRT CURBS

FOR 

THE MOST COMPLETE 

AND CURRENT INFORMA

TION 

VISIT  

RENEW

AIRE.COM 

LE-SERIES

113

  111 1/4" Overall  

  69 1/8" Case  

  19 3/4"  

  22 1/2"  

73 3/8"

Lifting Lugs

2" Duct

Flange Typ.

   2" Typ.  

RTV

ONLY

FA

RA

FA

RTR

ONLY

FRONT VIEW

Pressure Ports

(4) Typ.

  162 5/8" Case  

  165 3/8" Overall  

OA Inlets,

OA Damper

Locations

(Optional)

RIGHT VIEW

  8 7/8"  

  27 3/4"  

  53 1/2"  

  64 5/8"  

  38 5/8"  

  25 1/4"  

65 5/8" Case

  71 1/8" Overall  

CL 5 1/4"

(2) 7/8"

Knockouts

CL 11 3/8"

(5) 7/8"

Knockouts

EA Outlet

E-Box

13 3/8" X 15 1/2"

Electrical

Connection

Cover

LEFT VIEW

Disconnect

Switch

FA (RTR)

48" X 24" 

Duct Receiving

Flange

  52 1/8"  

  49 3/8"  

  38 1/4"  

  65 1/4"  

  18 1/4"  

OA

OA

78 1/2"  Minimum

Blower Service

Area Typ.

111" Minimum

Service Area

36" E-Box

Minimum 

Service Area

69 3/4" Minimum

Service Area

EA

RA 

24" X 48"

Opening

TOP VIEW

RA Damper 

Location

(Optional)

FA (RTV)

(2) 16 1/8" X 16 3/8"

Openings

Door

Swing

Door

Swing

Door

Swing

Door

Swing

  21 1/4"  

  49"  

  155 1/4" O.D.  

  20"  

  25"  

  9 1/2"  

  151 1/2" I.D.  

  3"  

  64 1/4" O.D.  

  60 1/2" I.D.  

A

A

TOP VIEW

CURB LE8X

FA

RA

  1 7/8"  

  3"  

  14"  

CURB CROSS-SECTION A-A (TYP.)

1 1/2" X 1/4"

Neoprene Gasket
3/4" X 3 1/2"

Wooden Nailer

SECTION A-A

Model: LE8X RTV/RTR

Drawing Type: Unit Dimension

Version: MAY18

ABBREVIATIONS

EA: Exhaust Air to outside

OA: Outside Air intake

RA: Room Air to be exhausted

FA: Fresh Air to inside

RTV: Rooftop Vertical RA & FA

RTR: Rooftop Vertical RA Only

INSTALLATION ORIENTATION

Unit must be installed in orientation

shown.

NOTE:

1. UNLESS OTHERWISE SPECIFIED,

DIMENSIONS ARE ROUNDED TO THE 

NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT 

TO CHANGE WITHOUT NOTICE.

LE8X

RT (RTV/RTR)

   Energy Recovery Ventilator  

Standard

AIRFLOW CONFIGURATION

Available as shown:

UNIT MOUNTING & APPLICATION

Must be mounted as shown. Airstreams can not  

be switched.

EA

AR

AF

OA

HERT except 6x 8x, LERT

RTV

OA

AR

EA

FA

HERT except 6x 8x, LERT

RTR

FOR 

THE MOST COMPLETE 

AND CURRENT INFORMA

TION 

VISIT  

RENEW

AIRE.COM 

LE-SERIES

121

FA

RTR

ONLY

OA

RA

FA

RTV

ONLY

EA

FA

RTR

ONLY

73 3/8"

Lift Lugs

  4"  

  111 1/4" Overall  

  69 1/8" Case  

   2" Typ.  

2" Duct

Flange

Typ.

CL 2 1/4"

Wiring

Pressure

Ports

(4) Typ.

  4 1/2"  

  93 5/8"  

  202 5/8" Case  

  205 3/8" Overall  

OA Inlets

OA Damper

Locations

(Optional)

  37 7/8"  

  44 5/8"  

  69 5/8" Case  

  71 1/8" Overall  

  29 5/8"  

  53 1/2"  

  47 1/4"  

  84 5/8"  

  9"  

CL 5 1/4"

(2)  7/8"

Knockouts

CL 11 3/8"

1 1/8"

Knockouts

E-Box

Disconnect

Switch

13 3/8" X 15 1/2"

Electrical

Connection

Cover

FA (RTR)

48" X 24"

Duct Receiving

Flange

  49 3/8"  

69 3/4" Minimum

Service Area

  72 1/8"  

36" E-Box

Minimum

Service Area

111" Minimum

Service Area

79 7/8" Minimum Blower Service  Area Typ.

  18 1/4"  

  58 1/4"  

  85 1/4"  

OA

OA

EA

RA 

24" X 48"

Opening

Door

Swing

Door

Swing

Door

Swing

RA Damper 

Location

(Optional)

Door

Swing

FA (RTV)

(2) 16 1/8" X 16 3/8" 

Openings

  64 1/4" O.D.  

  41 1/8"  

  49"  

  195 1/4" O.D.  

  20"  

  9 1/2"  

  25"  

  3"  

  60 1/2" I.D.  

  191 1/2" I.D.  

A

A

TOP VIEW

CURB LE10X

FA

RA

  1 7/8"  

  14"  

  3"  

SECTION A-A

1 1/2" X 1/4"

Neoprene Gasket

3/4" X 3 1/2"

Wooden Nailer

CURB CROSS-SECTION A-A (TYP.)

TOP VIEW

FRONT VIEW

LEFT VIEW

RIGHT VIEW

Model: LE10X RTV/RTR

Drawing Type: Unit Dimension

Version: MAY18

ABBREVIATIONS

EA: Exhaust Air to outside

OA: Outside Air intake

RA: Room Air to be exhausted

FA: Fresh Air to inside

RTV: Rooftop Vertical RA & FA

RTR: Rooftop Vertical RA Only

INSTALLATION ORIENTATION

Unit must be installed in orientation

shown.

NOTE

1. UNLESS OTHERWISE SPECIFIED,

DIMENSIONS ARE ROUNDED TO THE

NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT

TO CHANGE WITHOUT NOTICE.

LE10X

RT (RTV/RTR)

   Energy Recovery Ventilator  

Standard

AIRFLOW CONFIGURATION

Available as shown:

UNIT MOUNTING & APPLICATION

Must be mounted as shown. Airstreams can not  

be switched.

EA

AR

AF

OA

HERT except 6x 8x, LERT

RTV

OA

AR

EA

FA

HERT except 6x 8x, LERT

RTR

Содержание LE-8X*INH Series

Страница 1: ...SHIPPING RIGGING HOISTING AND ASSEMBLY MANUAL ENERGY RECOVERY VENTILATORS RENEWAIRE COM LE6X LE8X LE10X...

Страница 2: ...ll lifting lugs provided must be used Never lift the unit or modules from the top of the unit This unit is intended for general ventilating only Do not use to exhaust hazardous or explosive materials...

Страница 3: ...ATION AND MAINTENANCE MANUAL RENEWAIRE COM OWNER INFORMATION IMPORTANT USER INFORMATION SAVE THIS MANUAL In the unlikely event that factory assistance is ever required information located on the unit...

Страница 4: ...OODS 16 4 8 INSTALL MERV 8 FILTERS 17 5 0 ROOFTOP CURB DIMENSIONS 18 5 1 LE6XRT CURBS 18 5 2 LE8XRT CURBS 18 5 3 LE10XRT CURBS 19 6 0 ROOFTOP UNIT DIMENSIONS 20 6 1 LE6XRTH F DIMENSION DRAWING 20 6 2...

Страница 5: ...ations 11 LE Rooftop Unit Base Bolt Locations 11 Alignment Spacer Bolt Location 11 Roof Beam Assembly Graphic 2 12 Roof Beam Assembly Graphic 1 12 Roof Beam Assembly Bolt Locations 12 Roof Cap Caulkin...

Страница 6: ...Shipping Location typ Hoods are assembled at the factory and then secured for shipment inside the ERV LE models can be delivered in two modules for on site assembly or as a complete unit additional c...

Страница 7: ...clearance between the cables and the cabinet or any of the equipment attached to the unit or modules Provide additional blocking or covering as required Secure hooks and cables at all lifting points...

Страница 8: ...AND MAINTENANCE MANUAL 1 800 627 4499 8 RIGGING www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewa...

Страница 9: ...ed unassembled for applications where modules must be manipulated separately If the unit was ordered unassembled then you will need to assemble the modules in the field Each module is labeled with a c...

Страница 10: ...disposed of along with the screws that held them in place www renewaire com 800 627 4499 support renewaire com Apply 1 2 X 1 gasket tape provided as shown below Gasket tape creates an airtight seal be...

Страница 11: ...N or base supports LE RT of the two adjacent modules Use 3 8 washers between the bolt head and the unit and between the nut and the unit Fasten the nuts to the bolts secure the bases of the two module...

Страница 12: ...nsert 1 4 20 x 1 00 Grade 5 zinc plated hex head bolts through the holes in the roof beam Secure the nuts to secure the roof section www renewaire com 800 627 4499 support renewaire com AFTER THE LIFT...

Страница 13: ...ewaire com A galvanized cap roof flange is provided to seal the roof seam and to maintain a water and airtight seal The cap roof flange is provided with pre drilled holes 12 X 75 hex head tek screw w...

Страница 14: ...l not to over tighten the screw www renewaire com 800 627 4499 support renewaire com Two 2 galvanized roof cap ends are provided to seal the top end of each module and maintain a water and airtight se...

Страница 15: ...n the electrical connection cover on the E Box side of the front module by removing screws in the access panel The access panel is located in the upper left corner of the front module to the left of t...

Страница 16: ...4499 support renewaire com www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewaire com Slide the top flange of the OA air hood beneath the roof panel over...

Страница 17: ...that when filters are installed the filter spacers may tend to fall off the end of the filter receiving channels If this happens simply install the spacers between the first two filters in from the d...

Страница 18: ...EA FA RTV 16 1 8 X 19 1 2 Opening 115 1 4 O D 64 1 4 O D 3 60 1 2 I D 17 1 4 33 20 25 9 1 2 A A TOP VIEW CURB LE6X FA RA LEFT VIEW Model LE6X RTV RTR Drawing Type Unit Dimension Version MAY18 LE6XRT...

Страница 19: ...Lugs 4 111 1 4 Overall 69 1 8 Case 2 Typ 2 Duct Flange Typ C L 2 1 4 Wiring Pressure Ports 4 Typ 4 1 2 37 7 8 44 5 8 69 5 8 Case 71 1 8 Overall 29 5 8 53 1 2 47 1 4 84 5 8 9 C L 5 1 4 2 7 8 Knockouts...

Страница 20: ...ard AIRFLOW CONFIGURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x L...

Страница 21: ...CONFIGURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x LERT RTR RENE...

Страница 22: ...GURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x LERT RTR RENEWAIRE...

Страница 23: ...ator Standard AIRFLOW CONFIGURATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain optio...

Страница 24: ...GURATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain options are selected FOR THE MOS...

Страница 25: ...ATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain options are selected FOR THE MOST C...

Страница 26: ...CORNER WEIGHTS AT LIFTING LUGS BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2086 579 580 464 463 2100 583 585 466 465 2218 625 630 483 480 5 HP 7 5 HP Options UNIT LF LR RR RF ADDITIONAL WEIGHT...

Страница 27: ...X INH Front Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 119 5 Lifting Lug CORNER WEIGHTS AT LIFTING LUGS BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 1984 569 433 424 558 19...

Страница 28: ...ng LE 8XRT_CORNER LE 8X RT Fron Corner Weigh 73 5 Lifting Lug LR RR LF RF 159 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2625 753 680 568 624 2645 745 737 578 585 2763 790 780 5...

Страница 29: ...ing LE 8X INH Front Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 159 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2495 727 524 521 723 2509 733 524 522 730 2627...

Страница 30: ...ro Corner Weigh LE10X RT_CORNE 73 5 Lifting Lug LR RR LF RF 194 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 3031 842 841 674 674 3045 847 846 676 676 3163 892 890 690 691 5 HP 7...

Страница 31: ...nt Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 194 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2859 819 665 616 759 2873 825 666 617 765 2990 874 676 628 812...

Страница 32: ...ulting in significant energy savings Our ERVs are competitively priced simple to install easy to use and maintain and have a quick payback They also enjoy the industry s best warranty with the lowest...

Отзывы: