DOC2012/2000en
46
Fig. 26 Electrodes
Check that the modulating combustion air/gas control linkages are in good working order and tha
t
there is no
play in the gas control spindle
.
Replace the various panels on the top of the boiler including the down draught diverter, replace the burner
trolley and clamp into position. Re-connect the electrical connectors to the connection box.
Re-commission the boiler as described in Section 6 commissioning.
Gas trains
Fig. 27 Gas train
Type:
17
-
77 Type:
90
-
122