6 Commissioning
6.1 General
COMMISSIONING OF THE BOILER MUST BE CARRIED OUT BY PROPERLY QUALIFIED AND AUTHORISED
PERSONNEL. OTHERWISE, THE GUARANTY WILL BECOME VOID.
Never deviate from the instructions in this manual.
Flushing the system
To prevent damage from rust, sealing compounds, sand, metal particles etc., the system must be flushed
thoroughly, before the system is switched on. Also ensure that the heat exchanger is free of any such deposits
after flushing the system.
Water heating system
-
fill the system up to the standard set pressure
-
bleeding the system
-
switch on all pumps and check for correct direction of rotation
-
close the stop-valves in the secondary groups
Electrical connection
-
check the boiler electrical connection
-
switch on the boiler with the ON/OFF switch
-
adjust the temperature regulator to the desired flow water temperature
Gas connection
-
open the gas service cocks
-
bleed the gas pipe
NB: Insure adequate ventilation during bleeding
-
connect the measuring equipment to check:
* static pressure
* burner pressure
* boiler ionisation current