Procedure
Release the fixings securing the gas train cover at the front of the boiler and remove carefully in the
upward direction. Disconnect all the plugs from the front electrical panel and release the quick clamps
at either side of the burner trolley. The burner trolley can now be withdrawn from underneath the boiler.
Release the fixing screw at the top of the right hand upper side panel covering the electrical controls.
Both the right hand and left hand upper side panels can now be removed by lifting upwards and off their
lower locating pegs. The front and rear upper panel can also now removed by lifting upwards off the
locating pegs exposing the down draught diverter and the top of the heat exchanger.
Boiler with burner trolley removed
Fig. 24 R2000 with burner trolley removed
1 Flue
outlet
socket
2 Down draught diverter
3 Front and rear upper panels
4 Draught diverter air supply opening
5 Boiler heat exchanger
6 Combustion
chamber
7 Combustion
chamber
insulation
Flueway
baffles