REMKO SLE 20 Скачать руководство пользователя страница 6

Heat of condensation

The energy transferred from the 
condenser to the air is composed 
of:

1.  Heat energy previously removed 

in the evaporator.

2.  Electrical motive energy.

3.  Heat of condensation released 

during liquefaction of the water 
vapour. 

For the change from a liquid to a 
gaseous state, energy is necessary  
This energy is called heat of 
evaporation.  
It does not cause any rise of 
temperature, it is only necessary 
for the change from a liquid to a 
gaseous state.  

Vice versa, energy is released 
during the liquefaction of 
gas, which is called heat of 
condensation. 

The amount of heat of evaporation 
and condensation is the same.

 

For water, this is:  
2250 kJ/kg (4.18 kJ = 1kcal)

This shows that a relatively large 
amount of energy is released 
through the condensation of water 
vapour.
If the moisture to be condensed 
is not introduced through evapo-
ration in the room itself, but from 
outside, e.g. via ventilation, the 
heat of condensation released in 
the process contributes towards 
room heating.

In drying processes, the heat ener-
gy is recirculated, which is consu-
med during evaporation and relea-
sed during condensation. 
During dehumidification of 
the supplied air, the amount of 
heat energy produced is greater 
than that expressed in a rise of 
temperature. 

The time necessary for drying 
normally does not depend only 
on the unit capacity, but is rather 
determined by the rate at which 
the material or parts of the build-
ing release their moisture.

Safety notices

The units were subjected to ex-
tensive material, functional and 
quality inspections and tests prior 
to delivery.

However, the units may constitute 
a hazard if used by untrained per-
sonnel, improperly or not for the 
intended purpose.

The following information must 
be observed:

■   

The units must not be installed 
or operated in locations subject 
to explosion hazards

■   

The units must not be installed 
and operated in atmospheres 
containing oil, sulphur or salt

■   

The units must not be exposed 
to direct water jets

■   

The air inlet and outlet must al-
ways be kept free

■   

The air intake grilles must al-
ways be kept free of dirt and 
loose objects

■   

The units must not be covered 
during operation

■   

Never insert foreign objects into 
the units

■   

All electrical cables outside the 
units must be protected against 
damage (e.g. by animals, etc.)

ATTENTION

All work on the refrigeration 
system and electrical 
equipment must be referred to 
an authorised specialist!

■   

The units must only be installed 
or mounted in the intended po-
sition (horizontal)

■   

Free and frost protected 
condensate drain must always 
be ensured

■   

The unit connections must al-
ways be established in compli-
ance with the applicable instal-
lation regulations

6

REMKO SLE 20

Содержание SLE 20

Страница 1: ...Edition GB T03 REMKO SLE 20 Swimming pool dehumidifier Operation Technology Spare parts...

Страница 2: ......

Страница 3: ...pted Dehumidification 4 6 Safety notices 6 Description of the unit 7 Installation 8 Commissioning 9 Decommissioning 10 Care and maintenance 10 Troubleshooting 11 Electrical wiring diagram 12 Refrigera...

Страница 4: ...r escaping from buildings or materials is absorbed by the ambient air This increases their moisture content and ultimately results in corrosion mould rot peeling of paint coatings and other unwanted m...

Страница 5: ...uilding materials or structures can absorb substantial amounts of water e g bricks 90 190 l m heavy concrete 140 190 l m lime sand bricks 180 270 l m The drying out of moist materials e g masonry take...

Страница 6: ...ise of temperature The time necessary for drying normally does not depend only on the unit capacity but is rather determined by the rate at which the material or parts of the build ing release their m...

Страница 7: ...tion openes integrated at the bottom of the front panel This is transported via a filter evaporator and condenser Heat is extracted from the room air on the cold evaporator and cooled to below the dew...

Страница 8: ...at the bottom of the unit The condensate drain must be connected to the supplied drain connection not fitted A solid or flexible drain connection can be connected The drain hose must always be instal...

Страница 9: ...screws on the sides of the housing Route the cable of the electromagnetic switch through the diaphragm sleeve at the bottom of the unit and connection to terminal 13 and 14 on the control board Refit...

Страница 10: ...should be heavily fouled these can be cleaned carefully with soapy water Do not use a direct jet of water e g high pressure cleaner etc Do not use caustic cleaning agents or those containing solvents...

Страница 11: ...ee The unit operates but no condensate forms Check room temperature The operating range of the unit is between 3 C and 30 C Check the air humidity min 40 relative humidity is necessary Check the sucti...

Страница 12: ...2 Electronic control board Legend M1 Compressor M2 Fan TS1 Condenser sensor TS2 Evaporator sensor Y1 Solenoid valve Legend 1 Compressor 2 Evaporator 3 Condenser 4 Capillary tube 5 Dry filter 6 Solenoi...

Страница 13: ...0 9 Front panel 1109142 2 1 3 4 5 6 8 9 7 Additional condensate container Where it is not possible or difficult to provide a natural condensate drain the unit can be provided with an additional conden...

Страница 14: ...reserve the right to make changes to dimensions and the design in the interest of technical advances Diagram of unit SLE 20 21 10 12 13 15 2 1 23 19 24 25 26 3 9 28 6 8 4 14 27 22 16 17 14 REMKO SLE...

Страница 15: ...Electronics cover 1109109 15 Solenoid valve complete 1109110 16 Condenser NTC sensor 1109111 17 Evaporator NTC thermistor metal 1109112 19 Mains cable with plug 1109124 21 Condenser 1109114 22 Evapor...

Страница 16: ...is not liable for any damage attributed to failure to observe the manufacturer s instructions or applicable statutory requirements or unauthorised changes to the unit ATTENTION Copyright Reproduction...

Страница 17: ...de to the supplied unit without our prior permission Name of manufacturer REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 D 32791 Lage Unit machine type Permanently installed dehumidifier Ser...

Страница 18: ...nature 17 Date Signature 18 Date Signature 19 Date Signature 20 Date Signature Remarks Unit type Serial number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Unit cleaned outside Unit cleaned insi...

Страница 19: ...ntity g 190 Power supply V Hz 230 1 50 Max nominal current consumption A 2 1 Max power input kW 0 39 Sound pressure level LpA 1m 1 dB A 46 Depth mm 240 Width mm 535 Height mm 600 Weight kg 28 EDP No 6...

Страница 20: ...st a good reliable supplier REMKO a partner who helps solve problems Sales REMKO not only has an extensive sales network in Germany and abroad but also unusually highly qualified sales experts REMKO f...

Отзывы: