Check the IPM board
Switch the unit off and wait until the condensers are completely discharged. Disconnect the cables from the
IPM board and measure the resistances between P and UVWN, UVW and N.
Voltmeter
Normal resistance
Voltmeter
Normal resistance
(+) Red
(-) Black
¥
Multiple MOhm
(+) Red
(-) Black
¥
Multiple MOhm
P
N
U
N
U
V
V
W
W
(+) Red
Check the resistance values for the fan motor on the indoor unit
Use a multimeter to check the resistance values.
A
A
B
B
C
C
1
Fig. 31: Measurement of resistance values
1: Connection terminals
A: red
B: black
C: white
Item
Resistance value
YKSS-68-4-15-1
(Weilng)
Black - red
285.8Ω ±8% (20 °C)
Red - yellow
178.5Ω ±8% (20 °C)
Yellow - blue
178.5Ω ±8% (20 °C)