Error P6: Inverter board safety shut-down
(part 2)
Inverter board safety
shut-down
YES
Check the voltage
between the inverter
board's P and N termi-
nals. Is this between
277-366 VDC (SKT 520
AT) or 277-410 VDC
(larger versions)?
YES
See the first part of this table on
the previous page!
NO
Check the power supply
to the mains cable. Is
this between 208-230
V?
NO
Correct the power
supply. Is the system
running normally?
YES
Are the power supply's
cables fitted correctly? Is
the neutral wire correct?
NO
NO
Tighten the cable. Error rectified?
YES
Are all electrical connections in
the electrical box connected cor-
rectly?
NO
NO
Correct the electrical connection.
YES
NO
Check that the rectifier is functioning. To do this, use a multi-
meter to measure between the two terminals. The resistance
value should be 0.
YES
NO
Check the electrical con-
nections for the rectifier.
Are these correctly
implemented?
Replace the rectifier.
NO
Replace the electrical
connections.
YES
47