Error P3: Compressor current consumption too high
Safety shut-down due to
increased current consump-
tion on the compressor.
Switch the unit off, switch it
back on and measure the
total current consumption.
Is this within the specified
range?
YES
Check the cooling cycle. Is
this OK?
YES
Switch the unit off.
YES
Is the outside temperature
higher than 50 °C?
NO
Clean the condenser.
YES
Is the condenser dirty?
NO
Problem solved.
YES
Replace the control board.
Is the unit running nor-
mally?
NO
YES
Replace the entire electrical
box.