3
Design and function
3.1 Unit description
In cooling mode, the outdoor unit serves to output
the heat extracted by the indoor unit from the room
being cooled. In heating mode, the heat taken up
by the outdoor unit can be discharged by the
indoor unit into the room to be heated. In both
operating modes, the output produced by the com-
pressor precisely matches requirements, and
thereby regulates the nominal temperature with
minimal temperature deviations. This "inverter
technology" results in energy savings over conven-
tional split systems and also reduces noise emis-
sions to a particularly low level. The outdoor unit
can be installed in an outdoor area or, providing
that certain requirements are met, an indoor area.
The indoor unit is designed to be mounted high up
on the wall, in indoor areas. It is operated by an
infrared remote control. The outdoor unit consists
of a cycle with a compressor, fin condenser, three
electronic expansion valves and a condenser fan.
The outdoor unit can be combined with REMKO
indoor units from the series SKT 260 IT that pro-
vide sufficient cooling capacity. The outdoor unit
cooling cycle is controlled by the controller of the
indoor unit. In order to enable operation of the unit
at low outside temperatures, a thermal condenser
pressure regulator serves as winter fan speed con-
trol to regulate the speed of the condenser fan.
Floor consoles, wall consoles and refrigerant pipes
are available as accessories.
TCE
TCE
TCE
2
1
4
3
5
8
9
10
11
6
7
TCE
12
13
Fig. 8: Cooling cycle schematic
1:
Condenser
2:
Condenser fan
3:
Reversing valve
4:
Compressor
5:
Capillary tube throttle element
6:
Suction pipe connection valve A
7:
Suction pipe connection valve B
8:
Suction pipe connection valve C
9:
Suction pipe connection valve D
10: Injection pipe A
11: Injection pipe B
12: Injection pipe C
13: Injection pipe D
REMKO series SKT
14