5.5 Minimum clearances
Observe the minimum clearances to allow access
for maintenance and repair work and facilitate
optimum air distribution.
2
1
A
B
C
D
E
Fig. 15: Minimum clearances for outdoor unit
1: Air inlet
2: Air outlet
SKT 520-1060
A
100
B
1200
C
600
D
150
E
600
All measurements in mm
5.6 Oil return measures
If the outdoor unit is installed at a higher level than
the indoor unit, suitable oil return measures must
be taken. Usually, an oil pump bend is installed for
every 7 metres of height difference.
1
A
B
2
Fig. 16: Oil return measures
A: Outdoor unit
B: Indoor unit
1: One oil pump bend in suction pipe to outdoor
unit every 7 metres of height difference, radius:
50 mm
2: Max. 10 m
REMKO series SKT
20
Содержание SKT 1060 AT