REMKO DZ 18 HD Скачать руководство пользователя страница 6

Installation Instructions

 

 
The units are generally to be operated in accordance  
with the safety rules, the building code of the land con-
cerned and the fire protection code. 

Avoid under or overpressure in the room where the 
unit is installed, as this would result in combustion 
troubles. 

Suction and blow-out cross sections may not be re-
duced 

It is prohibited to connect conduits or hoses to the 
unit blow-out opening. 

Make sure that the technical regulations for combus-
tible liquids are observed when mobile fuel holders 
are installed. 

Outside Installation

 

The units are to be installed outside and to be pro-
tected from atmospheric effects to avoid damage. 

Make sure that no danger or inadmissible annoy-
ance is caused by the operation of the unit. 

Room Heating 

For room heating, hot air generators may only be op-
erated with a room thermostat (accessories). 

Make sure that sufficient fresh air is fed to ensure  
perfect combustion. Fresh air is to be fed preferably 
through windows and doors or through sufficiently di-
mensioned openings in the outer wall. 

Safety Distances 

Make sure to observe the following safety distances 
to ensure a safe operation of the unit: 

      –    towards the top, fire-retarding ceiling            1,5 m 

      –    towards the sides, non-burning objects         0,6 m 

      –    blow-off side, with non-burning objects         3,0 m 

      –    suction side, for perfect air supply                 1,0 m 

The floor and the ceiling must be from fire-retarding 
materials. 

Electric Connection 

The unit are operated with 230 V alternating current. 

Electric connection is carried out via a fitted mains 
cable with shockproof plug. 

Possibly required extension cables must be selected 
according to the existing cable length, the unit’s con-
necting line and the intended purpose. 

G

 

The electric connection of the unit is to be carried 
out via a special supply point with fault current 
safety switch. 

Starting 

 
Prior to starting, the unit is to be checked to make sure 
that there are no visible defects on the control and 
safety devices, that the unit has been installed correctly 
and that it has been properly connected to the mains. 

A properly trained person is to be charged with the op-
eration and control of the unit. 

Install unit in a stable position. 

Make sure that combustion air is supplied. 

Make sure that the air can be sucked in and be ex-
hausted freely. 

Avoid overpressure and underpressure in the room 
where the unit has been installed. 

Make sure that enough fuel is supplied. 

Fill fuel tank with clean fuel oil EL or diesel with the 
unit switched off. 

Use only appropriate and clean tanks to fill with fuel. 

Fuel filter

 

Prior to commissioning the unit and before 
the tank is filled each time, the main filter (F) 
must be checked for the presence of grime 
or the accumulation of paraffin. 

The main filter is positioning beside the filler. 

Make sure to fill the fuel tank only with the 
tank filter inserted into the filler neck. 

Paraffin accumulation by low outside temperatures 

The supply of sufficient liquid fuel is to be ensured, even 
with low outside temperatures. 

G

 

Paraffin accumulation can occur even at tempera-
tures as low as 5 °C. Appropriate measures must 
be taken to avoid this. 

The built-in tank heating is only active as long as the 
mains plug is connected with a functioning mains 
socket. 

It is not possible to get rid of paraffin discharge 
which is already present using the tank heating.  

The requirement for this is the cleaning of the entire 
fuel system.

 

G

 

The unit is to be installed only in well aerated 
rooms, but not in living rooms or similar recreation 
rooms! 

G

 

All extension cables are to be used only after 
having been removed from the roller.

 

1.   Put operating switch 

1

 into “0” 

position (OFF). 

2.   Connect unit plug to a suitable 

mains socket. 

230V/1~  50 Hz.

 

Connect the unit with the current supply 

Содержание DZ 18 HD

Страница 1: ...REMKO powerful like a bear REMKO DZ 18 HD Automatic oil heater Edition GB M04 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...t list 11 Wiring diagram 12 Service and guarantee 12 Troubleshooting 13 Maintenance log 14 Automatic oil heater REMKO DZ 18 HD Make sure to read these instructions carefully before starting using the...

Страница 4: ...upply air fan contin ues running for some time to cool down the combustion chamber and then it stops automatically Depending on the required heat rate the function de scribed above is repeated automat...

Страница 5: ...ated in rooms and areas where the danger of fire or explosion ex ists 3 Room drying 3 1 In deviation from point 2 3 in order to dry rooms with an air supply sufficient for the combustion heating units...

Страница 6: ...a special supply point with fault current safety switch Starting Prior to starting the unit is to be checked to make sure that there are no visible defects on the control and safety devices that the...

Страница 7: ...ng set the pressure Fuel Pump The standard type of the pump runs in a system of 1 pipe The required fuel is sucked in through the suction line S For the first starting and after having emptied the fue...

Страница 8: ...ervals Maintenance and Service The unit is to be maintained regularly whereby some fundamental rules are to be observed to ensure a long service life and trouble free operation After each heating peri...

Страница 9: ...hoto cell and ignition cable and remove the burner head by turning from the rear wall of the burner chamber 3 When maintenance has been carried out re assemble all parts carefully in reverse order 4 P...

Страница 10: ...31 24 26 27 25 28 33 34 36 37 37a 42 41 47 48 50 49 46 13 44 15 19 43 6 3 2 45 9 10 18 4 8 14 35 5 39 38 40 32 51 52 54 53 22 We reserve the right to make modifications in dimensions and construction...

Страница 11: ...with plug 1101320 25 traction relief 1108325 26 bridge circuit plug 1101019 27 thermostat socket 1101018 28 fan housing 1101803 29 filler cap 1101716 30 fuel filter filler neck 1101717 31 control IC...

Страница 12: ...r or his customer has filled in completely the guarantee certificate which is enclosed with every REMKO heater and has returned it to REMKO GmbH Co KG in due time after the unit s sale and commissioni...

Страница 13: ...ng dimension type size Replace nozzle take care of correct type and size 11 Wrong setting of ignition electrodes or damaged insulation Adjust correctly resp replace it 12 Air flow plate of the burner...

Страница 14: ...ge Check fastening screws Electric safety inspections Test run Model Model No Setting and maintenance work is to be carried out only by authorised specialists Remarks 1 Date 2 Date 3 Date 4 Date 5 Dat...

Страница 15: ......

Страница 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: