SLV 11 to SLV 33

Turning to left

 (

)  

= smaller scale value

larger

 pressure behind the 

baffle plate

lower

 power range

Turning to the right

 (

+

)  

= larger scale value

smaller

 pressure behind 

the baffle plate

upper

 power range

 

From SL 44 to SL 88

Turning to the left

 (

+

)

= larger scale value

smaller

 pressure behind 

the baffle plate

upper

 power range.

Turning to the right

 (

)

= smaller scale value

larger

 pressure behind the 

baffle plate

lower

 power range.

Adjusting the secondary air
(Nozzle fitting adjustment)

Carry out the presetting of the 
secondary air as follows:

Set the nozzle fitting 2 to the 
desired value with the adjusting 
screw 1.

Air flap

The quantity of combustion air 
required is adjusted by means of 
the adjusting screw 3.
The air flap is set according to 
the unit capacity and the further 
burner settings.

Adjustment of the air flap

Adjust the air flap as follows: 

1.   Loosen the knurled nut 4.
2.   Set the adjusting screw 3 

accordingly.

 

Turn to the right = Less air

 

Turn to the left = More air

4.   After having set the adjusting 

screw 3 lock it again with the 
knurled knob 4.

Additional notes

   If the flame should give off 

sooty smoke or break away 
with a fully opened air flap, 
reduce the pressure behind the 
baffle plate with the help of the 
secondary air setting

   It may also be necessary to 

open the air inlet nozzle further

Setting the pump pressure

The pump pressure should be 
adjusted, and checked if necessary, 
during burner commissioning and 
during all maintenance work. 

Adjust the pump pressure as 
follows: 

1.   Remove the stopper on the 

measurement nozzle "P".

2.   Fit a suitable oil pressure 

manometer here.

3.   Open all oil shut-off devices.

4.   Switch on the burner.

5.   Set the required oil pressure in 

accordance with the nozzle size 
and the unit capacity.

6.   Switch off the burner after 

completing the adjustments.

7.   Remove the oil pressure 

manometer again.  
Re-fit stopper incl. seal.

3

4

1

2

All values provided are only preliminary settings and must be adapted or calibrated in accordance with the exhaust gas analysis.

NOTE

Never let the pump run for 
extended periods without any 
fuel. Never leave the units for 
extended periods with a pump 
that has run dry.

CAUTION

If the burner should carry out 
a fault shut-down once again 
after the start phase, then 
another reset should be carried 
out after a waiting period of 5 
minutes has passed. 

Further reset procedures must 
be prohibited as there is a 
danger of deflagration. 

!

Содержание CLK 120

Страница 1: ...Operating and installation instructions Edition GB Q04 Read the instructions prior to performing any task CLK 30 CLK 50 CLK 70 CLK 120 CLK 150 REMKO CLK series Automatic oil gas heaters...

Страница 2: ......

Страница 3: ...prints Safety notes 4 Unit description 5 Specifications for fan assisted heaters 6 Installation instructions 7 Safety device 8 Exhaust gas ducting 9 Before commissioning 10 Commissioning 11 Shutdown 1...

Страница 4: ...ces Personnel must not remain in the installation area Appropriate prohibition signs must be displayed at the entrances Portable fuel containers must only be set up and used in observance of the techn...

Страница 5: ...ining the temperature of frost sensitive goods Heating ventilating or frost protection of lightweight structures Heating ventilating or frost protection of tents Heating or frost protection in garden...

Страница 6: ...he unit or the power supply Precipitation such as rain or snow can be sucked in through the supply air fan For this reason suitable weather protection should be provided When using the units the respe...

Страница 7: ...lled in well ventilated spaces and not in living areas or similar recreational areas NOTE The electrical connection for the units must be made at a separate feed point with a residual current device i...

Страница 8: ...damaged as well as if an overtemperature of ca 220 C is reached the filling medium will be emptied and the safety device is permanently triggered Resetting is no longer possible The controller is no...

Страница 9: ...order to exclude the ingress of rainwater and dirt If the units are used for room heating then the combustion gases must be routed away to the outside if necessary The exhaust gas ducting must be des...

Страница 10: ...pieces that may be being used Only suitable air distributors or air distributors approved by ourselves should be used for the air distribution The units should be checked for visible defects on the op...

Страница 11: ...t spots forming Membrane hoses must not be twisted Enclosed spaces being heated via hoses must not present any overpressure The forced air burner can be switched off briefly during operation by the te...

Страница 12: ...ct the plug 3 of the room thermostat 4 with the thermostat socket 1 on the unit 3 Place the room thermostat 4 at a suitable location in the room The thermostat sensor must not be located directly in t...

Страница 13: ...eplace contaminated filter if necessary Check the units for mechanical damage and have defective parts properly replaced Check the fan blades and combustion chamber with heat exchanger for contaminati...

Страница 14: ...screw the fuel filter 3 including the fuel lines and take the plug 4 off the burner 5 4 Loosen the 2 lower fastening screws on the burner flange 6 4 Loosen the clamping screw 7 on the burner flange 6...

Страница 15: ...then reset the automatic burner 9 Move the operating switch to the II Ventilate position If the supply air fan now starts up the fault may well be in the burner area Forced air burner and power suppl...

Страница 16: ...s are processed the majority of which are recyclable You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environment friendly manner Therefore...

Страница 17: ...green H2 External burner fault lamp red KL Terminal block M Fan motor RT Thermostat socket S1 Operating switch S2 Reset button burner STB Safety temperature limiter TR Temperature controller TW Temper...

Страница 18: ...66 67 68 69 70 71 72 4 11 25 63 27 REMKO oil filter standard up to CLK 70 with oil burner fitted ex works Available as option for all types REMKO Multiflex oil preheating Standard with CLK 120 150 wi...

Страница 19: ...Burner housing 1104724 1104724 1104759 1104789 1104789 35 Support foot 1104725 1104725 1104725 1104790 1104790 36 Axle 1104726 1104726 1104760 1104791 1104791 37 Wheel 1101621 1101621 1101621 1108369...

Страница 20: ...ta for the required oil nozzle size Air inlet nozzle The required blower pressure can be adjusted with the adjustable air inlet nozzle A in accordance with the combustion chamber resistance and chimne...

Страница 21: ...e off sooty smoke or break away with a fully opened air flap reduce the pressure behind the baffle plate with the help of the secondary air setting It may also be necessary to open the air inlet nozzl...

Страница 22: ...y by authorised specialists and in accordance with the legal provisions 1st BImSchV A corresponding measurement log should be generated Unit to be maintained only by authorised specialists in accordan...

Страница 23: ...0 000 0 000 0 000 0 000 0 000 in Stand By mode elSB kW 0 000 0 000 0 000 0 000 0 000 Pilot flame power requirement Ppilot kW N A N A N A N A N A Thermal efficiency at nominal heating capacity th nom...

Страница 24: ...400 500 500 Flue gas connection mm 150 150 150 200 200 Dimensions Length mm 1 450 1 450 1 610 2 100 2 100 Width mm 660 660 730 920 920 Height mm 1 000 1 000 1 120 1 350 1 350 Weight without blower oi...

Страница 25: ...25 Notes...

Страница 26: ...26 REMKO CLK SERIES...

Страница 27: ...27...

Страница 28: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Отзывы: