14
REMKO CLK SERIES
5. Slide the flame tube of the
burner into the burner flange.
Note dimension X in the
sketch!
6. Clamp the flame tube firmly
into place with the clamping
screw 7 whilst lifting the burner
slightly (3° tilt).
7. Lastly, tighten the bottom 2
fastening screws firmly.
8. Remount the fuel filter insert
and lines and check for leaks.
9. Re-fit burner cladding and
fasten with the quick couplings.
Additional notes for maintenance
of the unit
■
All work must be carried out
exclusively by authorised
specialists with the appropriate
equipment.
A log should be created and
kept safely by the operator
■
It is essential that the forced-air
burner is serviced and adjusted
by authorised specialists
Inspection cover
■
Always check that the seal
is correctly seated in the
inspection cover.
■
When fitting the inspection
cover ensure that the fastening
nuts are tightened evenly.
Unevenly tightened fixing nuts
can result in leaks.
Cleaning the combustion chamber
1. Set the operating switch to the
"0" position and remove the
power plug from the mains
socket.
2. Remove the burner
cladding 1 after
opening the two
quick-release couplings
2.
3. Unscrew the fuel filter 3
including the fuel lines and take
the plug 4 off the burner 5.
4. Loosen the 2 lower fastening
screws on the burner flange 6.
4. Loosen the clamping screw
7 on the burner flange 6 and
take out the burner by pulling
towards the front.
Burner up to size 33:
X = 20 mm
Burner from size 44:
X = 30 mm
s
s
s
X
6
7
3
4
6
2
1
5
5. Set down the burner and the
fuel filter carefully beside the
unit.
6. Remove the burner flange 6.
7. Take care not to damage
the flange seals, as far as is
possible.
Damaged flange seals can
result in incorrect air induction.
8. Clean the combustion chamber
through the burner opening
with a vacuum cleaner.
A special boiler cleaning set for
the REMKO industrial vacuum
cleaner is available as an
accessory.
Installation of the burner flange
and the burner
1. Check the flange seal and
replace if necessary.
2. Fix the burner flange to the unit
housing with the four fastening
screws.
Note the "UP"
sign!
3. Tighten the top 2 fastening
screws firmly.
4. Gently tighten the lower 2
fastening screws with only light
force so that the burner flange
can still be pulled together.
CAUTION
An electrical safety check must
be carried out in accordance
with VDE 0701 after any work
on the units.
NOTE
The restrictions on exhaust
gas losses per §10 of the
ordinance on small furnace
systems (1st. BImSchV) must
be observed.
!