Start up

After all components are 
connected and tested, the system 
can be put into operation. To 
ensure proper function, a function 
test should be made to recognize 
any irregularities during operation 
of the units before transfer to the 
client.

 
Function test and test run 

Check the following points.

■ 

Leak tightness of refrigerant 
lines.

■ 

Even run of compressor and 
fan.

■ 

Discharge of cold air on the 
interior unit and heated air on 
the exterior unit during cooling 
operation. 

■ 

Function test of the interior unit 
and all program runs.

■ 

Check of the surface 
temperature of the suction 
line and determination of 
evaporator overheating. To 
measure the temperature, hold  
the thermometer to the suction 
line and subtract the boiling 
point temperature reading on 
the pressure gauge from the 
measured temperature.

■ 

Documentation of the 
measured temperatures in the 
start up protocol.

Function test of Cooling 

operating mode

1.  Remove the caps on the valves.

2.  Start operation by opening 

the blocking valves of the 
exterior unit momentarily until 
the pressure gauge shows a 
pressure of approx. 2 bar. .

3.  Check all connections for leaks 

with leak detection spray and 
suitable leak detectors.

4.  If not leaks are found, open the 

blocking valves by turning them 
in counterclockwise direction 
with a hexagon wrench to the 
stop. If leaks were found, draw 
off the refrigerant and rework 
the defective connection. In 
this case, a new vacuum and 
drying procedure is imperatively 
required!

5.  Turn the main switch on the 

building or the fuse on.

6.  Turn the unit on via the remote 

control and select the cooling 
mode, maximum fan speed and 
lowest nominal temperature.

7.  Measure all required values, 

record them in the start up 
protocol and check the safety 
functions.

8.  Check the unit control with 

the functions described in 
chapter  „Operation“. 
Timer, temperature setting, fan 
speed and change between air 
circulation or dehumidification 
mode.

9.  Check the function of the 

condensation line by pouring 
distilled water into the 
condensation pan.    
To do so, use a spout to guide 
the water into the condensation 
pan.

10. Switch the interior unit to 

cooling mode.

11. Check all regulating, control 

and safety devices for function 
and correct adjustment during 
the test run.

12. Check the control of the 

interior unit with the functions 
described in the operating 
instructions   
(Timer, temperature 
adjustments and all mode 
settings).

13. Measure the overheating, 

external, internal, discharge and 
evaporator temperatures and 
record the test data in the start 
up protocol.

14. Remove the pressure gauge 

and install the caps.

The start up may only be 
made by especially trained 
technicians and must be 
documented accordingly.

      NOTE

Due to the turn on delay, the 
compressor will start up a few 
minutes later.

      NOTE

Then check the blocking valves 

for leaks.

      NOTE

Final tasks 

■ 

Reinstall all parts which were 
removed.

■ 

Familiarize the operator with 
the system.

27

Содержание ATY 260

Страница 1: ...Edition GB T08 REMKO ATY ATY 260 ATY 350 Wall room air conditioner in split design Operation Technology Spare parts...

Страница 2: ......

Страница 3: ...recycling 4 Warranty 4 Transport and packaging 5 Product description 5 Operation 6 13 Shut down 14 Care and maintenance 14 15 Troubleshooting and customer service 16 17 Assembly instructions for tech...

Страница 4: ...can cause malfunctions The units and components may not be operated in areas with increased danger of damage The minimum clearances must be observed The electrical power supply must be matched to the...

Страница 5: ...tor evaporator fan regulation and condensation pan Floor consoles wall consoles refrigerant lines and condensation pumps are available as accessories Unit description The units are delivered in strong...

Страница 6: ...stomer service Note Replace discharged batteries immediately with a new set to prevent battery leakage For longer down times we recommend removal of the batteries Note Display on interior unit The dis...

Страница 7: ...rature 4 Air circulation mode In this mode the air in the room is recirculated 5 Dehumidification mode In this mode the room is mainly dehumidified the adjusted temperature is retained FAN button With...

Страница 8: ...and heating mode In automatic mode the fixed temperature is reduced with the button from 24 C by 1 or 2 C and increased by 1 or 2 C with button The current setting is shown next to the temperature dis...

Страница 9: ...s the cooling function off To protect the compressor the regulation only turns the cooling on again after a waiting period of 3 minutes Cooling mode COOLING OPERATION MODE In the air circulation mode...

Страница 10: ...illating function The air distribution in the room is improved with the swing function SWING button covered SWING SWING SWING The fan speed can be adjusted with this button A selection can be made bet...

Страница 11: ...IMER button several times the turn on the turn off and the combined turn on and off timer is activated The turn on or turn off time blinks The timer display on the interior unit lights up The desired...

Страница 12: ...the timer can be set to 30 minutes 1 hour 2 hours 3 hours or 5 hours The current time is replaced by the still remaining time OFF OFF OFF With this button the air volume flow in cooling and heating o...

Страница 13: ...t the nominal temperature does not change DISP button covered DISP C C The unit is equipped with an ion generator to create negative ions A high concentration of negative ions is found for example in...

Страница 14: ...isconnected CAUTION Care Keep the interior unit and the exterior unit free of dirt plant covers and other deposits Clean the units only with a damp cloth Do not use harsh abrasive or solvent containin...

Страница 15: ...an with lukewarm water 2 Open the lower display cover on the front side of the unit by pressing both latches and carefully fold the cover downward and remove it from the bracket Fig 3 3 Push the clips...

Страница 16: ...e transmission Is it working after turning any possible interfering sources off No signal transfer at simultaneous operation of interfering sources Button of remote control stuck dual button control D...

Страница 17: ...r circulation sensor on interior unit is defective triggered Contact dealer E3 blinks Antifreeze sensor interior unit defective triggered Contact dealer E4 blinks Evaporator fan motor speed too low de...

Страница 18: ...rs then refrigerant has to be added For the quantity of additional refrigerant refer to chapter Add refrigerant Only use the union nuts for the refrigerant lines provided in the delivery scope and rem...

Страница 19: ...he ground Rain For attic or roof set up the unit should be installed with at least 10 cm ground clearance A floor bracket is available as optional equipment Sun The evaporator fins of the exterior uni...

Страница 20: ...ugh opposite sufficiently large air openings Fig 7 Minimum clearances The minimum clearances are to be provided for maintenance and repair work and for optimum air distribution ATY 260 AT ATY 350 AT A...

Страница 21: ...ow 8 Recheck the horizontal alignment of the unit 9 Reassemble the unit Installation of the interior unit The wall bracket for the unit must be attached with suitable screws and anchors Installation T...

Страница 22: ...ention to the installation instructions for the brackets 6 Make sure that no body vibration is transferred to part of the building Body vibration transfers are reduced by vibration dampers 7 Remove th...

Страница 23: ...f the interior unit and the length of the refrigerant lines however the procedure takes at least 60 minutes When foreign gases and moisture have been completely removed from the system the valves on t...

Страница 24: ...supply to the interior unit and a control line to the exterior unit with appropriate safeguards We recommend to install a main repair switch on the building near the interior unit The power supply is...

Страница 25: ...t cover 2 Remove the side wall at the connection 3 Guide the line through the edge protection ring of the fixed connection plate 4 Connect the line according to the wiring schematic 5 Anchor the line...

Страница 26: ...s and insulation for damage Check the electrical connection between the interior unit and the exterior unit for correct polarity Check all mountings suspensions etc for proper support and correct leve...

Страница 27: ...ant and rework the defective connection In this case a new vacuum and drying procedure is imperatively required 5 Turn the main switch on the building or the fuse on 6 Turn the unit on via the remote...

Страница 28: ...AT ATY 350 AT Dimensional and design changes to advance technical progress are reserved ATY 260 IT ATY 350 IT 265 245 532 148 567 567 All measurements in mm All measurements in mm 720 623 495 470 396...

Страница 29: ...12 7 Associated interior unit ATY 260 IT ATY 350 IT Operating range C 16 to 32 16 to 32 Adjustment range Cooling C 18 to 30 18 to 30 Adjustment range Heating C 16 to 28 16 to 28 Air volume per stage m...

Страница 30: ...05 1107405 7 Air outlet fins set 1107406 1107406 8 Condensation pan 1107439 1107439 9 Fin evaporator 1107408 1107409 10 Fan wheel evaporator 1107410 1107410 11 Fan motor evaporator 1107442 1107443 12...

Страница 31: ...22 1107422 3 Fan motor evaporator 1107423 1107424 4 Evaporator fin 1107425 1107426 5 Side section right 1107427 1107427 6 Compressor cpl 1107428 1107429 7 Condenser compressor evaporator fan 1107430 1...

Страница 32: ...les staff REMKO staff members in the field are more than just sales people Above anything they are able to advise our customers about cooling and heating technology Customer service Our units operate...

Отзывы: