Selection of the installation 
location

The interior unit is designed for 
horizontal wall installation in the 
upper wall area (at least 1.75 m 
from the upper edge - floor). 
However, it can also be used in the 
upper wall area above doors.

The exterior unit is designed 
for horizontal base installation 
externally. The placement location 
of the unit must be horizontal, 
level and firm. In addition, the unit 
must be secured to prevent it from 
tipping over. The exterior unit can 
be set up outside as well as inside 
a building. For external installation, 
please observe the following 
notes to protect the unit from 
atmospheric conditions.

Wall openings

■ 

A wall opening of at least 70 
mm diameter and 10 mm slope 
from the inside to the outside 
must be made for each interior 
unit.

■ 

We recommend to pad the hole 
inside or to cover it for example 
with a PVC pipe to avoid 
damage to the lines.

■ 

After installation, the wall 
opening should be closed off on 
the building side with a suitable 
sealant. Do not use cement or 
lime containing substances!

Installation material

The interior unit is attached with 4 
screws on the building side, through 
the back wall of the unit. 

The exterior unit is attached with 
4 screws via a wall bracket on 
the wall or a floor bracket on the 
ground.

Rain 

For attic or roof set up, the unit 
should be installed with at least 
10 cm ground clearance. A floor 
bracket is available as optional 
equipment.

Sun

The evaporator fins of the exterior 
unit are the heat discharge 
components in cooling operation. 
Sun exposure increases the 
temperatures of the fins and 
therefore reduces the heat 
discharge for the evaporator 
fins. The exterior unit should be 
set up on the north side of the 
building, if possible.  If necessary, 
a shade should be installed on the 
side of the building. This can be 
something like a small roof.  
However, the discharging warm air 
flow may not be affected by the 
measures.

Wind

If the unit is installed in windy 
areas, then it should be ensured 
that the building discharged warm 
air flow is carried away with 
the main wind direction. If this 
is not possible, wind protection 
should be installed on the building 
site. Make sure that the wind 
protection does not affect the air 
supply to the unit.

20 cm

Snow

Minimum distance to snow

Wind protection

Wind

Snow

In areas with heavy snowfall, you 
should install the unit on a wall.

The installation should be at least 
20 cm above expected snow levels 
to avoid infiltration of snow into 
the exterior unit. A wall bracket is 
available as optional equipment.

Lines in wall opening

Control line

Condensation line

Injection line

Suction line

PVC pipe

Install the exterior unit 
with appropriate anchors, 
depending on the type of wall

.

      NOTE

19

Содержание ATY 260

Страница 1: ...Edition GB T08 REMKO ATY ATY 260 ATY 350 Wall room air conditioner in split design Operation Technology Spare parts...

Страница 2: ......

Страница 3: ...recycling 4 Warranty 4 Transport and packaging 5 Product description 5 Operation 6 13 Shut down 14 Care and maintenance 14 15 Troubleshooting and customer service 16 17 Assembly instructions for tech...

Страница 4: ...can cause malfunctions The units and components may not be operated in areas with increased danger of damage The minimum clearances must be observed The electrical power supply must be matched to the...

Страница 5: ...tor evaporator fan regulation and condensation pan Floor consoles wall consoles refrigerant lines and condensation pumps are available as accessories Unit description The units are delivered in strong...

Страница 6: ...stomer service Note Replace discharged batteries immediately with a new set to prevent battery leakage For longer down times we recommend removal of the batteries Note Display on interior unit The dis...

Страница 7: ...rature 4 Air circulation mode In this mode the air in the room is recirculated 5 Dehumidification mode In this mode the room is mainly dehumidified the adjusted temperature is retained FAN button With...

Страница 8: ...and heating mode In automatic mode the fixed temperature is reduced with the button from 24 C by 1 or 2 C and increased by 1 or 2 C with button The current setting is shown next to the temperature dis...

Страница 9: ...s the cooling function off To protect the compressor the regulation only turns the cooling on again after a waiting period of 3 minutes Cooling mode COOLING OPERATION MODE In the air circulation mode...

Страница 10: ...illating function The air distribution in the room is improved with the swing function SWING button covered SWING SWING SWING The fan speed can be adjusted with this button A selection can be made bet...

Страница 11: ...IMER button several times the turn on the turn off and the combined turn on and off timer is activated The turn on or turn off time blinks The timer display on the interior unit lights up The desired...

Страница 12: ...the timer can be set to 30 minutes 1 hour 2 hours 3 hours or 5 hours The current time is replaced by the still remaining time OFF OFF OFF With this button the air volume flow in cooling and heating o...

Страница 13: ...t the nominal temperature does not change DISP button covered DISP C C The unit is equipped with an ion generator to create negative ions A high concentration of negative ions is found for example in...

Страница 14: ...isconnected CAUTION Care Keep the interior unit and the exterior unit free of dirt plant covers and other deposits Clean the units only with a damp cloth Do not use harsh abrasive or solvent containin...

Страница 15: ...an with lukewarm water 2 Open the lower display cover on the front side of the unit by pressing both latches and carefully fold the cover downward and remove it from the bracket Fig 3 3 Push the clips...

Страница 16: ...e transmission Is it working after turning any possible interfering sources off No signal transfer at simultaneous operation of interfering sources Button of remote control stuck dual button control D...

Страница 17: ...r circulation sensor on interior unit is defective triggered Contact dealer E3 blinks Antifreeze sensor interior unit defective triggered Contact dealer E4 blinks Evaporator fan motor speed too low de...

Страница 18: ...rs then refrigerant has to be added For the quantity of additional refrigerant refer to chapter Add refrigerant Only use the union nuts for the refrigerant lines provided in the delivery scope and rem...

Страница 19: ...he ground Rain For attic or roof set up the unit should be installed with at least 10 cm ground clearance A floor bracket is available as optional equipment Sun The evaporator fins of the exterior uni...

Страница 20: ...ugh opposite sufficiently large air openings Fig 7 Minimum clearances The minimum clearances are to be provided for maintenance and repair work and for optimum air distribution ATY 260 AT ATY 350 AT A...

Страница 21: ...ow 8 Recheck the horizontal alignment of the unit 9 Reassemble the unit Installation of the interior unit The wall bracket for the unit must be attached with suitable screws and anchors Installation T...

Страница 22: ...ention to the installation instructions for the brackets 6 Make sure that no body vibration is transferred to part of the building Body vibration transfers are reduced by vibration dampers 7 Remove th...

Страница 23: ...f the interior unit and the length of the refrigerant lines however the procedure takes at least 60 minutes When foreign gases and moisture have been completely removed from the system the valves on t...

Страница 24: ...supply to the interior unit and a control line to the exterior unit with appropriate safeguards We recommend to install a main repair switch on the building near the interior unit The power supply is...

Страница 25: ...t cover 2 Remove the side wall at the connection 3 Guide the line through the edge protection ring of the fixed connection plate 4 Connect the line according to the wiring schematic 5 Anchor the line...

Страница 26: ...s and insulation for damage Check the electrical connection between the interior unit and the exterior unit for correct polarity Check all mountings suspensions etc for proper support and correct leve...

Страница 27: ...ant and rework the defective connection In this case a new vacuum and drying procedure is imperatively required 5 Turn the main switch on the building or the fuse on 6 Turn the unit on via the remote...

Страница 28: ...AT ATY 350 AT Dimensional and design changes to advance technical progress are reserved ATY 260 IT ATY 350 IT 265 245 532 148 567 567 All measurements in mm All measurements in mm 720 623 495 470 396...

Страница 29: ...12 7 Associated interior unit ATY 260 IT ATY 350 IT Operating range C 16 to 32 16 to 32 Adjustment range Cooling C 18 to 30 18 to 30 Adjustment range Heating C 16 to 28 16 to 28 Air volume per stage m...

Страница 30: ...05 1107405 7 Air outlet fins set 1107406 1107406 8 Condensation pan 1107439 1107439 9 Fin evaporator 1107408 1107409 10 Fan wheel evaporator 1107410 1107410 11 Fan motor evaporator 1107442 1107443 12...

Страница 31: ...22 1107422 3 Fan motor evaporator 1107423 1107424 4 Evaporator fin 1107425 1107426 5 Side section right 1107427 1107427 6 Compressor cpl 1107428 1107429 7 Condenser compressor evaporator fan 1107430 1...

Страница 32: ...les staff REMKO staff members in the field are more than just sales people Above anything they are able to advise our customers about cooling and heating technology Customer service Our units operate...

Отзывы: