ATTENTION
Troubleshooting
Repair work on the electrical installation and on the burner must be performed exclusively by authorised
specialists for safety reasons.
Malfunctions
Cause:
The supply air fan does not start.
2 – 3 – 4 – 6 – 7 – 8 – 25
The supply air fan runs but the burner does not ignite.
The unit malfunctions without generating a flame.
1 – 5 – 6 – 9 – 10 – 11 – 12 – 13 – 14 – 15 – 16 – 17
20 – 21 – 23 – 24 – 26
The unit switches off during operation.
(The fault lamp in the automatic burner lights up)
4 – 5 – 6 – 7 – 8 – 9 – 10 – 11 – 13 – 15 – 16 – 17
19 – 20 – 21 – 22 – 23 – 24 – 26
Smoke formation during operation.
7 – 10 – 11 – 13 – 15 – 17 – 19 – 21 – 22 – 24
The unit does not switch off in operating switch position "0".
18 – 25
Cause:
Remedial measures:
1. Air in fuel system during start-up.
Press the fault key of the automatic burner.
Repeat if necessary (max. 3 times).
2. The unit is not connected to the electricity supply.
Check the power plug, mains socket and mains voltage.
3. No plug in the thermostat socket.
Connect the thermostat/strapping plug to the thermostat socket.
4. The room thermostat is set too low.
Set the room thermostat higher than room temperature.
5. The fault lamp in the automatic burner lights up.
Reset the automatic burner by pressing the malfunction button.
6. Malfunction in the automatic burner.
Replace the automatic burner.
7. The motor is overloaded.
(The fan runs irregularly or is blocked)
Allow the motor to cool.
Check the smooth running of the fuel pump.
Check the electrical and mechanical functioning of the motor.
8. The fuel pump is blocked.
Check the fuel pump and replace if necessary.
9. The fuel tank is empty.
Fill the fuel tank with clean EL heating oil or diesel.
10. The fuel filter is contaminated.
Replace the fuel filter.
11. The nozzle is blocked or of the wrong size.
Replace the nozzle (ensure correct type and size)!
12. The electrodes are incorrectly set, the insulation has cracked.
Adjust and replace if necessary.
13. The air slide of the burner head has moved or is contaminated.
Adjust using CO
2
indicator and soot pump.
(CO
2
: 11 - 12%, soot level in acc. with Bacharach: 0 - 1).
14. The solenoid valve does not open.
Check the solenoid valve and replace if necessary.
The STB has triggered or is faulty.
15. The pump pressure is improperly set.
Replace the pump coupling.
16. The pump coupling is faulty.
Replace the pump coupling.
17. Leak in the intake line or fuel filter.
Check and replace faulty parts if necessary.
18. The solenoid valve does not close.
Disconnect the fuel line at the main filter, the flame extinguishes.
19. The protection grid on the supply air fan is contaminated.
Clean the protection grid.
20. Shutdown by safety temperature limiter (STB).
Check the intake protection grid and clean if necessary.
Reset the STB and automatic burner.
21. Air bubbles in fuel system.
Start the unit to discharge the air through the nozzle.
Repeat this procedure up to 3 times if necessary.
22. Insufficient ventilation.
Open door or window.
23. The photocell is contaminated or faulty.
Clean the photocell and replace if necessary.
24. Improper exhaust gas routing.
See chapter "Exhaust gas routing".
25. Operating switch malfunction.
Check the operating switch and replace if necessary.
26. Paraffin precipitation in the heating oil.
Clean the entire burner system.
See also chapter "Commissioning".