11

All sizes are approximate values and are in mm.

The optimum setting must be 
adapted to the unit-specific 
conditions.

NOTE

Use only suitable tools to 
remove the oil nozzle and 
use the nozzle mounting for 
resistance!

2 - 3

7

7

Setting the ignition electrodes

Setting the air slide

The air slide is factory set.  
The combustion air may only be 
adjusted to the unit-specific or 
local conditions by an authorised 
and

 

qualified technician.

After loosening the clamping 
screw [K], the air slide is fine 
adjusted by means of exhaust gas 
measurement.

Burner head

Air slide

K

approx. 4 - 5 mm

Cleaning the cartridge filter

Clean the cartridge filter [B] of 
the fuel pump at regular intervals 
and/or replace as necessary.

1.   Turn the stopper [C] upwards 

out of the pump using a 
hexagon wrench.

2.   Carefully remove the cartridge 

filter [B] from the stopper.

3.   Clean and/or replace 

the cartridge filter [B].

4.   Push the filter back onto 

the stopper and screw both 
back into the pump.

ATTENTION

Never let the pump run for 
extended periods without any 
fuel. Never leave the units for 
extended periods with a pump 
that has run dry.

Exhaust gas analysis

To perform the exhaust gas 
analysis, the exhaust gas 
measuring instrument probe must 
be placed in the centre of the heat 
exchanger pipe port.

Fig. Exhaust gas connection

Setting the pump pressure

The pump pressure may only 
be set and/or modified when 
a suitable oil pressure gauge is 
connected to the connection [P]
The pump pressure is modified by 
turning the pressure adjustment 
screw [A]:
Clockwise:

 

Increase pressure
Anti-clockwise:
Decrease pressure

The pump pressure is determined 
according to the heating capacity 
of the unit and the size of 
the nozzle.

CO

value:

  approx. 11 - 12%;

Soot level:

 0 - 1 in acc. with 

Bacharach

A

P

U

Return flow

Inlet

C

B

Notes for implementing the 1st. 
BImSchV
Units that are not expected to 
be operated for longer than 3 
months in the same location 
are not subject to any approvals 
or monitoring as per the 1st. 
BImSchV.

The measurement may also be 
performed in an exhaust gas 
duct. For this, a corresponding 
measurement aperture must be 
created in the duct at a distance of 
approx. 300 mm behind the unit 
port.

Содержание ATK 50-S

Страница 1: ...Edition GB I02 REMKO ATK 50 S Automatic oil heater with built in oil burner tank and exhaust gas connection Operation Technology Spare parts...

Страница 2: ......

Страница 3: ...or on the unit itself Subject to modifications no liability accepted for errors or misprints Safety notes 4 Environmental protection and recycling 4 Unit description 5 Installation instructions 6 7 E...

Страница 4: ...ed by untrained personnel The following notes must be observed in full The power plug must be pulled out of the mains socket before maintenance and repair work The units may only be operated by person...

Страница 5: ...reset key 2 1 Unscrew the protective cap 1 2 Carefully press in the reset key 2 with a suitable tool 3 Screw the protective cap 1 back on again 4 Reset the automatic burner Operating sequence The sup...

Страница 6: ...ge due to inclement weather units installed outdoors must be adequately protected NOTE Overpressure and underpressure in the installation area should be avoided as this will inevitably lead to combust...

Страница 7: ...g the 1st BImSchV Units that are not expected to be operated for longer than 3 months in the same location are not subject to any approvals or monitoring as per the 1st BImSchV The units can be transp...

Страница 8: ...suitable and clean fuels may be used ATTENTION In the event of defects that endanger the operational safety of the units operation of the units must be discontinued immediately and the supervisor inf...

Страница 9: ...e of the units The units including combustion chamber and burner must be cleared of soot deposits dust and dirt after every heating period or according to the operating conditions The oil filters must...

Страница 10: ...alues 7 Following maintenance work refit all parts carefully in reverse order NOTE When positioning the baffle plate 7 always ensure that the aperture 5 is not obscured by a strut on the plate s s s C...

Страница 11: ...e pump run for extended periods without any fuel Never leave the units for extended periods with a pump that has run dry Exhaust gas analysis To perform the exhaust gas analysis the exhaust gas measur...

Страница 12: ...s Exploded view of the unit B 69 B 54 52 53 32 34 35 97 31 99 39 98 42 41 123 111 116 100 117 15 22 119 101 102 104 103 105 30 18 11 A 80 1 125 126 95 92 121 27 24 28 19 70 23 40 114 90 113 50 112 122...

Страница 13: ...40 STB support bracket 1103981 104 Connection nipple 1 4 1111674 41 Cable gland 1103982 105 Connection nipple 1 8 1111672 42 Counter nut 1103983 111 Fuel filter one way 1102146 50 Combustion chamber...

Страница 14: ...fuel pump and replace if necessary 9 The fuel tank is empty Fill the fuel tank with clean EL heating oil or diesel 10 The fuel filter is contaminated Replace the fuel filter 11 The nozzle is blocked...

Страница 15: ...n max 1 kW 0 85 Electrical protection provided by the customer A 10 Sound pressure level LpA 1m 2 dB A 74 Exhaust connection mm 150 Dimensions Length mm 1535 Width mm 650 Height mm 1005 Weight kg 102...

Страница 16: ...must be advisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is...

Отзывы: