51
Correct gas/air setup:
18.1. Connect the flue gas analyser, ensuring the connections are gas tight.
18.2. Run the boiler at full-load by pressing ‘
m
’- and [
+
]-keys simultaneously.
18.3. When full-load speed is reached, check values against the table and adjust if
necessary using the
ß
screw on the venturi
(see Fig. 20).
Fig. 20
Setting screws
00.W4H.79.00005
Boiler
model
Natural gas
Fan speed
(approx. rpm)
O
2
CO
2
full
load
part
load
%
%
Quinta 85
6250
1250
3,4
+/- 0.1
9.5
+/- 0.1
Table 16 Setting data (with open air case)
ß
full-load setting screw
Þ
part-load setting screw