6.6.6 Interface selection (
(
)
Adjustable
00
or
01
, factory default
01
This value sets the control option.
01
for standard 0 -10 Volt external control and
rematic
®
series of compensators
(if fitted).
00
for the Honeywell Chronotherm option.
6.6.7 DHW cut-in temperature (
B
)
Adjustable from
01
to
20
°C (8 steps,
see Table 09
), factory default 5°C (
05
).
DHW demand:
With sensor:
- The DHW demand is satisfied when the DHW temperature equals the DHW set
point temp (parameter
#
) + 5°C.
- The DHW cut-in temperature sets the
∆
T below this end point for DHW demand.
Cut-in temperature = DHW set point (55) + 5 - parameter
B
(5)
i.e. 55 + 5 - 5 = 55°C.
With thermostat or
rematic
®
control: the thermostat or
rematic
®
control determines the
DHW demand.
Boiler modulation during continuing DHW demand
Sensor, thermostat and
rematic
®
control:
- The boiler will modulate when the flow temp equals the DHW set point + DHW
control stop set point (parameter
I
) i.e. 55+20 = 75.
- The boiler carries out a control stop at a flow temp of 80°C (modulation point + 5°C),
the display initally shows
980
, reducing to
975
.
- The DHW cut-in temperature sets the
∆
T below this control stop.
Cut-in temperature = DHW set point (55) + DHW control stop set point (parameter
I
)
+ 5 - parameter
B
(5)
i.e. 55 +20 + 5 - 5 = 75
6.6.8 Fan Speed at DHW full load (
C
)
Adjustable from 18% to 100% output (= approx. 1200 to 5300 rpm), factory default
53
(100%).
This value sets the maximum output of the boiler.
Parameters
D
-
E
- and
F
are factory set and must not be changed
6.6.9 Forced part load time after start (HTG only -
G
)
Adjustable from
00
-
15
min., factory default
03
(3 minutes).
This value sets the period of time the boiler will stay on part load at start up during
which time the flow temp is limited by part load temp set point (parameter
$
) Changing
the factory default should only be carried out on advice from the service engineer.