9 Troubleshooting
9.1
Error codes
The boiler is fitted with an electronic regulation and control unit. The
heart of the control system is a microprocessor, the
Comfort
Master
©
, which controls the boiler and also protects the boiler. If a
fault is detected anywhere in the boiler, the boiler locks out and the
display will show the fault code as follows:
In a red flashing display:
4
The symbol
c
4
The symbol
J
4
The fault code (for example
e[01
)
The meaning of the error codes is given in the error table. To do this,
proceed as follows:
4
Note the error code displayed.
The error code is important for rapid and correct tracking
of the type of problem and for any technical assistance from
Remeha
.
4
Press the
J
key for 2 seconds. If the error code continues to
display, search for the cause in the error table and apply the
solution.
If the display does not show
J
but rather
a
, the boiler
must be switched off and then switched on again after 10
seconds before the fault can be reset.
Code
Cause of
the fault
Description
Checking / solution
E
:
00
SU / PCU
PSU PCB not connected
Bad connection
4
Check the wiring between the PCU and PSU PCBs
PSU PCB faulty
4
Replace the PSU PCB
E
:
01
PSU
The safety parameters are
incorrect
Bad connection
4
Check the wiring between the PCU and PSU PCBs
PSU PCB faulty
4
Replace the PSU PCB
9. Troubleshooting
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
82
22/04/2016 - 300026141-001-07
Содержание CALORA TOWER GAS 15S EX
Страница 7: ...22 04 2016 300026141 001 07 5...
Страница 101: ...en Appendix Information on the ecodesign and energy labelling directives...
Страница 105: ...1 Specific information 300026141 ErP02 03052016 5...
Страница 106: ...1 Specific information 6 300026141 ErP02 03052016...
Страница 107: ......