n
Analogue output (0-10 V)
This outlet can be configured either for the temperature or the
output. The two controls are described briefly below.
A jumper (
1
) on the interface is used to select either temperature
control (
*
) or heat output control (
%
).
Jumper 1 Output signal (V) Temperature
À
Description
*
0,5
-
Alarm
1 - 10
10 - 100
Delivered temperature
Jumper 1 Output signal (V) Heat output (%) Description
%
0
0 - 15
Boiler off
0,5
15 - 20
Alarm
2,0 - 10
(1)
20 - 100
Heat output supplied
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
5.9.5.
Connection possibilities for the PCB (SCU-
S02)
n
Installing the PCB
SCU-S02
C003819-B
SCU-S02
PCU 192
SCU-S
n
Connecting the board
Connect the BUS connector on the SCU-S02 board to the PCU board
in the boiler.
T000800-A
1
2%
1
1
5. Installation
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
46
22/04/2016 - 300026141-001-07