Code
Cause of
the fault
Description
Checking / solution
E
:
11
SU/PCU
Difference between the flow
and return temperatures too
great
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
Bad connection
4
Check that the sensor has been correctly fitted
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
4
Check that the heating pump is operating correctly
E
:
12
SU/PCU
Maximum boiler temperature
exceeded (STB thermostat
maximum)
Bad connection
4
Check the wiring between the PCU PCB and the STB
4
Check that the SU PCB is correctly in place
4
Check the electrical continuity of the STB
4
Check whether the STB has been correctly fitted
Sensor fault
4
Replace the STB if necessary
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
E
:
14
SU
5 burner start-up failures
No ignition
4
Check the wiring between the PCU PCB and the ignition transformer
4
Check that the SU PCB is correctly in place
4
Check the ionization/ignition electrode
4
Check the earthing
4
SU PCB faulty: Change the PCB
Ignition arc, but no flame formation
4
Vent the gas flues
4
Check that the gas valve is fully opened
4
Checking the gas supply pressure
4
Check the operation and setting of the gas valve unit
4
Check that the air inlet and flue gas discharge flues are not blocked
4
Check the wiring on the gas valve unit
4
SU PCB faulty: Change the PCB
Presence of the flame but insufficient ionization (<3 µA)
4
Check that the gas valve is fully opened
4
Checking the gas supply pressure
4
Check the ionization/ignition electrode
4
Check the earthing
4
Check the wiring on the ionization/ignition electrode
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
9. Troubleshooting
22/04/2016 - 300026141-001-07
85
Содержание CALORA TOWER GAS 15S EX
Страница 7: ...22 04 2016 300026141 001 07 5...
Страница 101: ...en Appendix Information on the ecodesign and energy labelling directives...
Страница 105: ...1 Specific information 300026141 ErP02 03052016 5...
Страница 106: ...1 Specific information 6 300026141 ErP02 03052016...
Страница 107: ......