6.4
Gas settings
6.4.1.
Adapting to another gas type
WARNING
Only a qualified engineer may carry out the following
operations.
The boiler is preset in the factory to operate on natural gas H (G20).
For operation on another group of gases, carry out the following
operations:
4
Set the fan speed using the parameters
p17
,
p18
and
p19
.
¼
See chapter: "Parameter descriptions", page 68
4
Set the air/gas ratio.
4
Affix the label which indicates for which type of gas the boiler is
fitted and set.
6.4.2.
Checking and setting combustion
1. Unscrew the plug of the flue gas measurement point.
2. Insert the probe for the flue gas analyser into the measurement
opening.
WARNING
Ensure that the opening around the sensor is completely
sealed when taking measurements.
CAUTION
The flue gas analyser must have a minimum accuracy of
0,25% O
2
.
3. Remove the cover from the sealed chamber.
¼
see chapter: "Removing the cover from the sealed
4. Measure the percentage O
2
in the flue gases. Perform
measurements at full capacity and low capacity (Front panel
removed).
L000182-A
XXX
XXXX
XXXX
X
XXXX
XXXX
XXXXX
XXXX
XXXX
XXXX
XXXXX
XXXX
XXX
XXXX
XXXX
XXXXX
XX
XX
XXXXX
XXX
XXX
XXXX
XXXX
X
XXXX
XXXX
XXXXX
XXXX
X
XXXX
XXXX
XXXXX
XX
XX
XXXXX
X
1
M002534-A
1
2
6. Commissioning
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
60
22/04/2016 - 300026141-001-07