Parameter
Function
FLO
Displays the current calculated measured flow
FL-CAL
Used to enter the actual measured flow
FL-OVR
Used to override the current airflow setpoint
FI-MIN
Display/modify the minimum airflow setpoint
F-MAXO
Display/modify the maximum occupied airflow setpoint
F-MAXU
Display/modify the maximum unoccupied airflow setpoint
CW-CLS
Off
Actuator rotation counter-clockwise to close damper
On
Actuator rotation clockwise to close damper
Before using the Flow Tool to perform airflow calibration of a MACH-Air
™
or MACH-ProAir
™
controller, set the minimum (VAVx-FLO-MIN) and maximum airflow setpoints (VAVx-FLO-
MAX-OCC, the VAV box inlet duct diameter (VAVx-DIAM-IN) and the damper actuator
rotation direction to close (VAVx-CW-CLS).
The following MACH-Air
™
/MACH-ProAir
™
airflow calibration procedure as outlined in
Reliable Controls
®
Application Notice 0009 assumes a functional and configured controller.
The calibration procedure requires stable duct static pressure. The central air handling
system should be controlling to the design duct static pressure setpoint. Significant
changes to the VAV box inlet static pressure during the calibration procedure will result in an
inaccurate calibration. For best practice, set all connected VAV boxes to 50% of the
maximum flow setpoint using the FLO-SP-OVR variable.