![Reliable Controls SS-CO2-H-UD Скачать руководство пользователя страница 105](http://html1.mh-extra.com/html/reliable-controls/ss-co2-h-ud/ss-co2-h-ud_user-manual_1436213105.webp)
96
2004 – 2014 Reliable Controls
®
Corporation. All rights reserved.
F
IGURE
87: SS
ONBOARD
FLOW
CHART
WORKSHEET
PROGRAMMING
FOR
RESERVED
POINTS
The valid temperature range of an input for the SS-IO is limited between -40 to 120 °C
(-40 to 248 °F).
T
ABLE
20: SS P
ROGRAMMING
E
XAMPLE
P
OINT
L
IST
Point
Point Name
Type
Point Mnemonic
Editable
Point 1
VAV7-RmT
Analog
1VAR1
Can Change
Point 2
VAV7_RmT-Sp
Analog
1VAR2
Can Change
Point 3
Rm1-OVR
State
1VAR3
Can Change
Point 4
Rm1-Humidity
Analog
1VAR4
Can Change
Point 5
Rm1-Motion
State
1VAR5
Can Change
Point 6
Rm1-CO2
Analog
1VAR6
Can Change
All values that must be modifiable by the SS, including both onboard options and/or
operator modification, will have to be configured as
Can Change
.
5
Program each row of the
SMART-Sensor
worksheet with the desired points.
Points are mapped from a host controller to the SS by entering the point
descriptor, label or mnemonic in the Point column of the
SMART-Sensor
worksheet. Alternatively, points may be dragged from a host controller
worksheet and dropped in the desired Point cell on the
SMART-Sensor
worksheet.
New points can not be created in an SS. Every point used on an SS must already exist in a
MACH-System controller.