S
ECONDARY
P
OINT
D
ISPLAY
The
secondary point
can be configured to display an additional value and descriptive
abbreviation on the idle screen of the display in the top row. This can be useful for
displaying the value of important space or system conditions such as setpoint, humidity
or CO
2
from the host controller. Any of the ten SS-L display points can be selected as the
secondary display
.
T
O
CHANGE
THE
SECONDARY
DISPLAY
POINT
1
The
secondary point
display may also be configured using the SS-L Addressing
feature.
2
After the initialization sequence, hold the
and
buttons for five seconds,
release for two seconds, then press the
button.
3
The LCD screen displays SSADDR and the current address of the SS-L. Press
the
button to select the 2 DISP screen.
F
IGURE
46: SS-L
SECONDARY
DISPLAY
CONFIGURATION
SCREEN
4
Press the
or
to configure the desired SS-L point to be displayed as the
secondary point.
5
After the desired configuration is complete, allow the onboard configuration tool
to time-out. The LCD screen will revert to the standard operator display.