SS Programming Example
U
SER
G
UIDE
PROGRAMMI
NG AND CONFIGURATION EXAMPLES
SMART-S
ENSOR
™
2004 – 2014 Reliable Controls
®
Corporation. All rights reserved.
F
IGURE
86: SS
ONBOARD
OPTION
FLOW
CHART
SMART-Sensor
™
Onboard Options
Temperature
Slider
Override
Humidity
Map Remaining
Desired Points
A
B
C
D
NO
NO
NO
NO
YES
YES
YES
YES
Enter the appropriate variable (VAR) from the
host controller into Row 1 of the
SMART-
Sensor
worksheet and select the suitable
temperature range.
On -S models, the VAR used to map the
slider setpoint must be entered in Row 2.
On -O models, the VAR used to map the
override button must be entered in Row 3
with a Range set to
On/Off
.
On -H models, the VAR used to map relative
humidity must be entered in Row 4.
On -OC models, the VAR used to map the
motion sensor must be entered in Row 5.
See SS-L Product Bulletin 4294.
On -CO2 models, the VAR used to map the
CO
2
sensor must be entered in Row 6 with a
Range set to
PPM
.
On -IO models, the VAR used to map SS
input 1 must be entered on Row 7 and the
VAR used to map SS input 2 must be entered
on Row 8. The VAR used to map SS output 1
must be entered on Row 9 and the VAR used
to map SS output 2 must be entered on Row
10.
Motion
E
YES
NO
CO
2
D
NO
YES
I/O
E
YES
NO