INPUT/OUTPUT POINT OPTION (-IO)
SMART-Sensor
™
models with the -IO option feature two TRIAC outputs (except SS-DUCT models have
solid-state relays that switch AC or DC), and two onboard dry-contact/10k thermistor inputs. These
inputs and outputs may be used to connect ancillary space-related field devices without consuming
inputs and outputs on the host controller.
F
IGURE
63: I
NTERNAL
VIEW
OF
A
SS-S-IO
AND
SS-DUCT-IO
I
NPUTS
The SS-IO inputs may be used to connect either dry-contacts or 10 k thermistors. The field
devices wire directly to the input terminal block on the SS-IO. A variable (VAR) must be
created in the host controller to store the value of each input used. The variables that
represent the inputs are then referenced using row 7 and row 8 of the
SMART-Sensor
worksheet. To permit the SS-IO to define the values of these variables, the User Edit
column must be configured for
Can Change.
When the SS-IO inputs are configured for temperature, they have a maximum range of
-40 to 120
°
C (-40 to 248
°
F).